Can someone explain how this makes sense electrically?












9















The wiring in my house is... odd. Nearly every pair of outlets has one of the outlets connected to a light switch. Sometimes that switch is quite far from the outlet even when there are other closer switches that seem to control nothing at all. Sometimes that switch also controls overhead lighting, which makes no sense to me from a design standpoint. Sometimes that switch is a dimmer switch, which is a really horrible idea as if you plug anything other than a light bulb into it, like some electronics, the dimmer switch could do them a lot of damage. One such dimmer switch is also connected to a ceiling fan, and setting the switch to anything less than full does not change the speed of the fan, it just makes it a lot noisier (AC induction motor, obviously).



There are light fixtures that don't seem to have any power to them and aren't controlled by any switch, though I could believe the switch might just be hiding somewhere. There are also switches that seem to control absolutely nothing, though I could believe I just haven't found what they're connected to.



The oddest thing I have found though has to do with the circuit breakers around overhead lighting. I have a chandelier in my dining room that is connected to a dimmer switch. When I moved in, all of the bulbs were incandescents, and I wanted to be more energy efficient, so I replaced them all with dimmable LED bulbs. Now however, I could not turn the chandelier fully off, with the dimmer switch all the way down, the lights still dimly shone. This had never been an issue before, but I thought it probably meant the dimmer switch was faulty, and it was just the different voltage response curves of the incandescents versus the LEDs that meant it had never been noticed before, so I set out to replace the switch.



Now there are two circuit breakers that are relevant to this chandelier. One is labeled "dining room," the other is labeled "lights." As far as I can tell, the dining room breaker controls all of the outlets in the dining room area, while the lights breaker controls all of the overhead lighting in the house.



Here's where the odd part comes in. If I turn off the dining room breaker, the lights stay lit. I have turn off the lights breaker to switch off the lights. However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. In order to remove the power I was detecting, I have to also turn off the dining room breaker, even though the lights were staying on when I switched that off.



This conforms to no type of electrical theory with which I am familiar, though there might be some peculiarity of household wiring I don't know about that explains this. Can anyone tell me what might be going on?



Update 3/24/19: After replacing the dining room dimmer switch with one specifically designed for LEDs, those lights are now working quite well. Based on several people's advice in this question, I have now set out to replace the bedroom dimmer switches that are connected to outlets with toggle switches. Have run into additional issues detailed here.










share|improve this question









New contributor




Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





















  • Could you please add the mains voltage? (The difference of the 100 V to the mains voltage is relevant.) Also, the location - there are different local "traditions" of messing up wiring. In Germany, we have no wall switches at all. It can be messed up anyway. I have wall sockets in all rooms, and breakers in a central box, with labels on the breakers. But there is not much correlation between labels and socket locations.

    – Volker Siegel
    yesterday











  • My place has the same set up, lots of outlets connected to dimmer switches. its a huge pain, you have to make sure to never actually adjust the dimmers or it screws up what is plugged in.

    – chiliNUT
    yesterday











  • In many cases, the performance of LED or dimmable CFL lamps with a dimmer may be greatly improved by having a single incandescent, of essentially any wattage (even a 3W night-light bulb), in parallel with the LEDs. A similar situation applies with neon-lit switches (which are designed to glow when "off"). Figuring out a good place to put such a light may sometimes be tricky, but it can make some kinds of switches work better with LEDs.

    – supercat
    yesterday






  • 1





    How old is the house? Any idea about it's electrical history? Some old houses just had switches controlling outlets, with no overhead light at all, (expecting lamps to be used). I'd guess overhead lights & dimmers were installed at some later point, but still leaving the outlets essentially untouched. (Are the outlets even grounded, verified with a tester, not just seeing the right type of outlet?)

    – Xen2050
    yesterday











  • @VolkerSiegel The house is in the US, in California, line voltage is 110V.

    – Joel Croteau
    yesterday
















9















The wiring in my house is... odd. Nearly every pair of outlets has one of the outlets connected to a light switch. Sometimes that switch is quite far from the outlet even when there are other closer switches that seem to control nothing at all. Sometimes that switch also controls overhead lighting, which makes no sense to me from a design standpoint. Sometimes that switch is a dimmer switch, which is a really horrible idea as if you plug anything other than a light bulb into it, like some electronics, the dimmer switch could do them a lot of damage. One such dimmer switch is also connected to a ceiling fan, and setting the switch to anything less than full does not change the speed of the fan, it just makes it a lot noisier (AC induction motor, obviously).



There are light fixtures that don't seem to have any power to them and aren't controlled by any switch, though I could believe the switch might just be hiding somewhere. There are also switches that seem to control absolutely nothing, though I could believe I just haven't found what they're connected to.



The oddest thing I have found though has to do with the circuit breakers around overhead lighting. I have a chandelier in my dining room that is connected to a dimmer switch. When I moved in, all of the bulbs were incandescents, and I wanted to be more energy efficient, so I replaced them all with dimmable LED bulbs. Now however, I could not turn the chandelier fully off, with the dimmer switch all the way down, the lights still dimly shone. This had never been an issue before, but I thought it probably meant the dimmer switch was faulty, and it was just the different voltage response curves of the incandescents versus the LEDs that meant it had never been noticed before, so I set out to replace the switch.



Now there are two circuit breakers that are relevant to this chandelier. One is labeled "dining room," the other is labeled "lights." As far as I can tell, the dining room breaker controls all of the outlets in the dining room area, while the lights breaker controls all of the overhead lighting in the house.



Here's where the odd part comes in. If I turn off the dining room breaker, the lights stay lit. I have turn off the lights breaker to switch off the lights. However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. In order to remove the power I was detecting, I have to also turn off the dining room breaker, even though the lights were staying on when I switched that off.



This conforms to no type of electrical theory with which I am familiar, though there might be some peculiarity of household wiring I don't know about that explains this. Can anyone tell me what might be going on?



Update 3/24/19: After replacing the dining room dimmer switch with one specifically designed for LEDs, those lights are now working quite well. Based on several people's advice in this question, I have now set out to replace the bedroom dimmer switches that are connected to outlets with toggle switches. Have run into additional issues detailed here.










share|improve this question









New contributor




Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





















  • Could you please add the mains voltage? (The difference of the 100 V to the mains voltage is relevant.) Also, the location - there are different local "traditions" of messing up wiring. In Germany, we have no wall switches at all. It can be messed up anyway. I have wall sockets in all rooms, and breakers in a central box, with labels on the breakers. But there is not much correlation between labels and socket locations.

    – Volker Siegel
    yesterday











  • My place has the same set up, lots of outlets connected to dimmer switches. its a huge pain, you have to make sure to never actually adjust the dimmers or it screws up what is plugged in.

    – chiliNUT
    yesterday











  • In many cases, the performance of LED or dimmable CFL lamps with a dimmer may be greatly improved by having a single incandescent, of essentially any wattage (even a 3W night-light bulb), in parallel with the LEDs. A similar situation applies with neon-lit switches (which are designed to glow when "off"). Figuring out a good place to put such a light may sometimes be tricky, but it can make some kinds of switches work better with LEDs.

    – supercat
    yesterday






  • 1





    How old is the house? Any idea about it's electrical history? Some old houses just had switches controlling outlets, with no overhead light at all, (expecting lamps to be used). I'd guess overhead lights & dimmers were installed at some later point, but still leaving the outlets essentially untouched. (Are the outlets even grounded, verified with a tester, not just seeing the right type of outlet?)

    – Xen2050
    yesterday











  • @VolkerSiegel The house is in the US, in California, line voltage is 110V.

    – Joel Croteau
    yesterday














9












9








9


1






The wiring in my house is... odd. Nearly every pair of outlets has one of the outlets connected to a light switch. Sometimes that switch is quite far from the outlet even when there are other closer switches that seem to control nothing at all. Sometimes that switch also controls overhead lighting, which makes no sense to me from a design standpoint. Sometimes that switch is a dimmer switch, which is a really horrible idea as if you plug anything other than a light bulb into it, like some electronics, the dimmer switch could do them a lot of damage. One such dimmer switch is also connected to a ceiling fan, and setting the switch to anything less than full does not change the speed of the fan, it just makes it a lot noisier (AC induction motor, obviously).



There are light fixtures that don't seem to have any power to them and aren't controlled by any switch, though I could believe the switch might just be hiding somewhere. There are also switches that seem to control absolutely nothing, though I could believe I just haven't found what they're connected to.



The oddest thing I have found though has to do with the circuit breakers around overhead lighting. I have a chandelier in my dining room that is connected to a dimmer switch. When I moved in, all of the bulbs were incandescents, and I wanted to be more energy efficient, so I replaced them all with dimmable LED bulbs. Now however, I could not turn the chandelier fully off, with the dimmer switch all the way down, the lights still dimly shone. This had never been an issue before, but I thought it probably meant the dimmer switch was faulty, and it was just the different voltage response curves of the incandescents versus the LEDs that meant it had never been noticed before, so I set out to replace the switch.



Now there are two circuit breakers that are relevant to this chandelier. One is labeled "dining room," the other is labeled "lights." As far as I can tell, the dining room breaker controls all of the outlets in the dining room area, while the lights breaker controls all of the overhead lighting in the house.



Here's where the odd part comes in. If I turn off the dining room breaker, the lights stay lit. I have turn off the lights breaker to switch off the lights. However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. In order to remove the power I was detecting, I have to also turn off the dining room breaker, even though the lights were staying on when I switched that off.



This conforms to no type of electrical theory with which I am familiar, though there might be some peculiarity of household wiring I don't know about that explains this. Can anyone tell me what might be going on?



Update 3/24/19: After replacing the dining room dimmer switch with one specifically designed for LEDs, those lights are now working quite well. Based on several people's advice in this question, I have now set out to replace the bedroom dimmer switches that are connected to outlets with toggle switches. Have run into additional issues detailed here.










share|improve this question









New contributor




Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












The wiring in my house is... odd. Nearly every pair of outlets has one of the outlets connected to a light switch. Sometimes that switch is quite far from the outlet even when there are other closer switches that seem to control nothing at all. Sometimes that switch also controls overhead lighting, which makes no sense to me from a design standpoint. Sometimes that switch is a dimmer switch, which is a really horrible idea as if you plug anything other than a light bulb into it, like some electronics, the dimmer switch could do them a lot of damage. One such dimmer switch is also connected to a ceiling fan, and setting the switch to anything less than full does not change the speed of the fan, it just makes it a lot noisier (AC induction motor, obviously).



There are light fixtures that don't seem to have any power to them and aren't controlled by any switch, though I could believe the switch might just be hiding somewhere. There are also switches that seem to control absolutely nothing, though I could believe I just haven't found what they're connected to.



The oddest thing I have found though has to do with the circuit breakers around overhead lighting. I have a chandelier in my dining room that is connected to a dimmer switch. When I moved in, all of the bulbs were incandescents, and I wanted to be more energy efficient, so I replaced them all with dimmable LED bulbs. Now however, I could not turn the chandelier fully off, with the dimmer switch all the way down, the lights still dimly shone. This had never been an issue before, but I thought it probably meant the dimmer switch was faulty, and it was just the different voltage response curves of the incandescents versus the LEDs that meant it had never been noticed before, so I set out to replace the switch.



Now there are two circuit breakers that are relevant to this chandelier. One is labeled "dining room," the other is labeled "lights." As far as I can tell, the dining room breaker controls all of the outlets in the dining room area, while the lights breaker controls all of the overhead lighting in the house.



Here's where the odd part comes in. If I turn off the dining room breaker, the lights stay lit. I have turn off the lights breaker to switch off the lights. However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. In order to remove the power I was detecting, I have to also turn off the dining room breaker, even though the lights were staying on when I switched that off.



This conforms to no type of electrical theory with which I am familiar, though there might be some peculiarity of household wiring I don't know about that explains this. Can anyone tell me what might be going on?



Update 3/24/19: After replacing the dining room dimmer switch with one specifically designed for LEDs, those lights are now working quite well. Based on several people's advice in this question, I have now set out to replace the bedroom dimmer switches that are connected to outlets with toggle switches. Have run into additional issues detailed here.







electrical lighting circuit-breaker led dimmer-switch






share|improve this question









New contributor




Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question









New contributor




Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question








edited yesterday







Joel Croteau













New contributor




Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked yesterday









Joel CroteauJoel Croteau

1536




1536




New contributor




Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






Joel Croteau is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.













  • Could you please add the mains voltage? (The difference of the 100 V to the mains voltage is relevant.) Also, the location - there are different local "traditions" of messing up wiring. In Germany, we have no wall switches at all. It can be messed up anyway. I have wall sockets in all rooms, and breakers in a central box, with labels on the breakers. But there is not much correlation between labels and socket locations.

    – Volker Siegel
    yesterday











  • My place has the same set up, lots of outlets connected to dimmer switches. its a huge pain, you have to make sure to never actually adjust the dimmers or it screws up what is plugged in.

    – chiliNUT
    yesterday











  • In many cases, the performance of LED or dimmable CFL lamps with a dimmer may be greatly improved by having a single incandescent, of essentially any wattage (even a 3W night-light bulb), in parallel with the LEDs. A similar situation applies with neon-lit switches (which are designed to glow when "off"). Figuring out a good place to put such a light may sometimes be tricky, but it can make some kinds of switches work better with LEDs.

    – supercat
    yesterday






  • 1





    How old is the house? Any idea about it's electrical history? Some old houses just had switches controlling outlets, with no overhead light at all, (expecting lamps to be used). I'd guess overhead lights & dimmers were installed at some later point, but still leaving the outlets essentially untouched. (Are the outlets even grounded, verified with a tester, not just seeing the right type of outlet?)

    – Xen2050
    yesterday











  • @VolkerSiegel The house is in the US, in California, line voltage is 110V.

    – Joel Croteau
    yesterday



















  • Could you please add the mains voltage? (The difference of the 100 V to the mains voltage is relevant.) Also, the location - there are different local "traditions" of messing up wiring. In Germany, we have no wall switches at all. It can be messed up anyway. I have wall sockets in all rooms, and breakers in a central box, with labels on the breakers. But there is not much correlation between labels and socket locations.

    – Volker Siegel
    yesterday











  • My place has the same set up, lots of outlets connected to dimmer switches. its a huge pain, you have to make sure to never actually adjust the dimmers or it screws up what is plugged in.

    – chiliNUT
    yesterday











  • In many cases, the performance of LED or dimmable CFL lamps with a dimmer may be greatly improved by having a single incandescent, of essentially any wattage (even a 3W night-light bulb), in parallel with the LEDs. A similar situation applies with neon-lit switches (which are designed to glow when "off"). Figuring out a good place to put such a light may sometimes be tricky, but it can make some kinds of switches work better with LEDs.

    – supercat
    yesterday






  • 1





    How old is the house? Any idea about it's electrical history? Some old houses just had switches controlling outlets, with no overhead light at all, (expecting lamps to be used). I'd guess overhead lights & dimmers were installed at some later point, but still leaving the outlets essentially untouched. (Are the outlets even grounded, verified with a tester, not just seeing the right type of outlet?)

    – Xen2050
    yesterday











  • @VolkerSiegel The house is in the US, in California, line voltage is 110V.

    – Joel Croteau
    yesterday

















Could you please add the mains voltage? (The difference of the 100 V to the mains voltage is relevant.) Also, the location - there are different local "traditions" of messing up wiring. In Germany, we have no wall switches at all. It can be messed up anyway. I have wall sockets in all rooms, and breakers in a central box, with labels on the breakers. But there is not much correlation between labels and socket locations.

– Volker Siegel
yesterday





Could you please add the mains voltage? (The difference of the 100 V to the mains voltage is relevant.) Also, the location - there are different local "traditions" of messing up wiring. In Germany, we have no wall switches at all. It can be messed up anyway. I have wall sockets in all rooms, and breakers in a central box, with labels on the breakers. But there is not much correlation between labels and socket locations.

– Volker Siegel
yesterday













My place has the same set up, lots of outlets connected to dimmer switches. its a huge pain, you have to make sure to never actually adjust the dimmers or it screws up what is plugged in.

– chiliNUT
yesterday





My place has the same set up, lots of outlets connected to dimmer switches. its a huge pain, you have to make sure to never actually adjust the dimmers or it screws up what is plugged in.

– chiliNUT
yesterday













In many cases, the performance of LED or dimmable CFL lamps with a dimmer may be greatly improved by having a single incandescent, of essentially any wattage (even a 3W night-light bulb), in parallel with the LEDs. A similar situation applies with neon-lit switches (which are designed to glow when "off"). Figuring out a good place to put such a light may sometimes be tricky, but it can make some kinds of switches work better with LEDs.

– supercat
yesterday





In many cases, the performance of LED or dimmable CFL lamps with a dimmer may be greatly improved by having a single incandescent, of essentially any wattage (even a 3W night-light bulb), in parallel with the LEDs. A similar situation applies with neon-lit switches (which are designed to glow when "off"). Figuring out a good place to put such a light may sometimes be tricky, but it can make some kinds of switches work better with LEDs.

– supercat
yesterday




1




1





How old is the house? Any idea about it's electrical history? Some old houses just had switches controlling outlets, with no overhead light at all, (expecting lamps to be used). I'd guess overhead lights & dimmers were installed at some later point, but still leaving the outlets essentially untouched. (Are the outlets even grounded, verified with a tester, not just seeing the right type of outlet?)

– Xen2050
yesterday





How old is the house? Any idea about it's electrical history? Some old houses just had switches controlling outlets, with no overhead light at all, (expecting lamps to be used). I'd guess overhead lights & dimmers were installed at some later point, but still leaving the outlets essentially untouched. (Are the outlets even grounded, verified with a tester, not just seeing the right type of outlet?)

– Xen2050
yesterday













@VolkerSiegel The house is in the US, in California, line voltage is 110V.

– Joel Croteau
yesterday





@VolkerSiegel The house is in the US, in California, line voltage is 110V.

– Joel Croteau
yesterday










3 Answers
3






active

oldest

votes


















12















However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. … Can anyone tell me what might be going on?




Coupling between wires (inductance and capacitance in parallel wires).



You say you have strange long runs between outlets and switches — if any of these extra lengths run in parallel, this is a great environment for the voltage from one to be induced in the other if it's disconnected.



If you try putting a load, like a small light bulb, across that 100 V, it will vanish (read 0 V), because there is no significant current capacity in this coupling. It might even go away if you were to attach an analog voltmeter (which is more of a load because current from the line to move the needle) instead of a digital one (which typically has a 1 MΩ input impedance that presents almost no load).






share|improve this answer





















  • 3





    In other words - it's acting as an antenna.

    – J...
    yesterday











  • Note that even the induced voltage can still give you a noticeable electric shock, better not touch any wires where you are getting a 100 V reading.

    – user149408
    yesterday











  • It also could be due to a high resistance electrical connection between the wires.

    – Loren Pechtel
    yesterday



















7














Rundown in layman's terms:




  1. Light switch to outlet. You will see a lot of these in older homes. By code for a long time in a lot of areas you had to be able to turn on a light from a switch accessible when entering a room. Easiest and most cost-effective way to do this is put switch to outlet. I had six rooms in my house like this.


  2. Dimmer to outlet. For sure not code compliant. You are correct that it could damage electronics and could be a huge fire/safety issue. Please replace this with a regular switch ASAP - $5 for a quick fix while you work things out.


  3. Dimmer to ceiling fan. Can't do this. If the ceiling fan has two hots coming into the box from fan you can buy a fan control + dimmer. If there is only one hot then you just install a switch and it is off/on for both.


  4. Light switches doing nothing. You must do a complete mapping assessment of your house. With a house like this it might take 3-6 hours. But you have to turn off one circuit at a time and figure out what doesn't work. You must also for 100% sure make sure that each switch is tested for working on every light and outlet (have a known working bulb). Write down every outlet and switch in a spreadsheet marking room, location, what it controls, and circuit.


  5. You cannot expect to plug LED bulbs into old dimmers and expect them to work. You need to put in a dimmer that is suitable for the type of LED you are installing.


  6. The dining room lights - need more info.







share|improve this answer


























  • There are three bedrooms with dimmer switches connected to outlets and fans. I am just replacing them all with toggle switches. There are only the two wires coming into the switch box, so no way I can use any fancier switches without heavy rewiring.

    – Joel Croteau
    yesterday



















6














Switch switching outlets. That's normal enough. Often the outlet(s) switched are far from the switch, because that is where the installer thought you would want to put the light. The installer was wrong. They always are. Because of that some of them switch more than one receptacle.



Split receptacles. That is normal. That's what the "tab" between the brass screws is for. Leave the tab on, the 2 screws are an easy way to splice. Break it off, you control each socket with a separate hot. There's also a tab on the neutral side if you want the sockets on 2 separate circuits.



Dimmers on receptacles. No no no! For the reasons you stated and worse. You know what to do. If you were super attached to dimmable receptacles, they make specially keyed receptacles just for lamps.



Mystery lamps. Fair possibility the bulbs are burnt out (back in the old days, bulbs burned out, true fact) or there is something wrong with the fixture. They make wire tracing devices if you really want to dive into the mysteries.



Mystery switches. Aside from that they may control a broken lamp, sometimes that just happens as wiring gets revised. They may also control receptacles that you have not checked, outside lights you do not see (optionally: with burned out bulbs) etc. They may also be half of a miswired 3-way circuit that is miswired in a way only the other switch works. **3-way switches do not have the words "on" or "off" on them.



Glowing LEDs on dimmers. Actually, the incandescents also glowed, but only in infrared, so you would have needed to be an elf to see it. LEDs are so much more efficient (and glow only in the visible range) that it's much more obvious. The reason is many switch loops do not have neutral wires. That means dimmers cannot power themselves between supply and neutral; they must place themselves in series with the lamps. That works slick on incandescents.



By the way, some dimmers actually have a "hard off" or even "hard on" setting. It's not in the smooth working range of the dimmer. You have to push the knob harder past a detent to reach that position. Most people, it never occurs to them to push it that hard, so they never know it's there. The "hard off" is important so you can change the bulb safely. The "hard on" is nice because it stops the bulb from buzzing. Dimmers aren't variacs, and their waveform is real sawtoothey.



Grouping of lamp circuits. It is common and wise for lamps to be powered from a different circuit than receptacles. That way if you trip a breaker you are not also in the pitch black. It is extremely unusual for lighting to trip a breaker (especially if LED), however they need to be provisioned with a worst case scenario (all oversized incandescents) in mind, and 125% of that.



Crosstalk. This is plain old capacitive coupling. Lay two wires alongside each other, one energized with AC, one disconencted, this will "antenna" some microscopic current onto the other wire. Cheap DVMs are so sensitive they can see this. Use a traditional analog voltmeter and that it will extinguish that phantom voltage; there's not enough current behind the phantom voltage to move the jeweled meter movement.



Multi-wire branch circuits (MWBC). This is a pair of half-circuits wired using a common neutral. The two half-circuits must be 240V across the hots, with neutral in the middle. That way the neutral carries the difference in currents, and you can trust it won't exceed breaker value. Done wrong, neutral carries the sum of currents, which overloads it!



In any circuit, all wires must be carried in the same cable or conduit so currents in each direction cancel each other out. This is AC power: any gap will induce vibration and fatigue failure. All that is relevant because the phantom-voltage wire may well be half of an MWBC, which would explain the strong capacitive coupling.



There are additional rules with MWBCs. Neutrals must be pigtailed, not use a device like a receptacle as a splice point. The breakers must be handle-tied so they shut off together, but normally a 2-pole breaker is used.



I expect your double circuit (the one with the phantom voltage) is a MWBC, and the work was done back before handle ties were required.



MWBCs have fallen out of favor because they are difficult to use with AFCI or GFCI protection, which is now required on almost all circuits.






share|improve this answer


























  • Nerd disclaimer. "you would have needed to be an elf or halfling to see it"; halflings, while perceptive, sneaky, sure-footed, and good with thrown missiles, are not known for extraordinary vision like elves are.

    – Jimmy Fix-it
    yesterday











  • @JimmyFix-it The trait I was thinking of is infravision, or "not needing to buy a FLIR". It's been a long time but I thought I recalled in D&D lore, pretty much everyone but humans seems to have it lol.

    – Harper
    yesterday






  • 2





    you are so right. In Gygax's original AD&D they did have infravision. In subsequent iterations, alas, the doughty halflings seem to have lost this trait...

    – Jimmy Fix-it
    yesterday











  • @harper re the original dining room dimmer switch, it actually had a detente at the bottom of the switch range, but even below that, the lights were still glowing. If I pushed down on the switch when it was at the bottom of Its range, I could force the lights off, but as soon as I took my finger off, they would come back on. That's why I said I thought it was a faulty switch.

    – Joel Croteau
    21 hours ago











Your Answer








StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "73"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);

StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});

function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});


}
});






Joel Croteau is a new contributor. Be nice, and check out our Code of Conduct.










draft saved

draft discarded


















StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f160497%2fcan-someone-explain-how-this-makes-sense-electrically%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown

























3 Answers
3






active

oldest

votes








3 Answers
3






active

oldest

votes









active

oldest

votes






active

oldest

votes









12















However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. … Can anyone tell me what might be going on?




Coupling between wires (inductance and capacitance in parallel wires).



You say you have strange long runs between outlets and switches — if any of these extra lengths run in parallel, this is a great environment for the voltage from one to be induced in the other if it's disconnected.



If you try putting a load, like a small light bulb, across that 100 V, it will vanish (read 0 V), because there is no significant current capacity in this coupling. It might even go away if you were to attach an analog voltmeter (which is more of a load because current from the line to move the needle) instead of a digital one (which typically has a 1 MΩ input impedance that presents almost no load).






share|improve this answer





















  • 3





    In other words - it's acting as an antenna.

    – J...
    yesterday











  • Note that even the induced voltage can still give you a noticeable electric shock, better not touch any wires where you are getting a 100 V reading.

    – user149408
    yesterday











  • It also could be due to a high resistance electrical connection between the wires.

    – Loren Pechtel
    yesterday
















12















However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. … Can anyone tell me what might be going on?




Coupling between wires (inductance and capacitance in parallel wires).



You say you have strange long runs between outlets and switches — if any of these extra lengths run in parallel, this is a great environment for the voltage from one to be induced in the other if it's disconnected.



If you try putting a load, like a small light bulb, across that 100 V, it will vanish (read 0 V), because there is no significant current capacity in this coupling. It might even go away if you were to attach an analog voltmeter (which is more of a load because current from the line to move the needle) instead of a digital one (which typically has a 1 MΩ input impedance that presents almost no load).






share|improve this answer





















  • 3





    In other words - it's acting as an antenna.

    – J...
    yesterday











  • Note that even the induced voltage can still give you a noticeable electric shock, better not touch any wires where you are getting a 100 V reading.

    – user149408
    yesterday











  • It also could be due to a high resistance electrical connection between the wires.

    – Loren Pechtel
    yesterday














12












12








12








However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. … Can anyone tell me what might be going on?




Coupling between wires (inductance and capacitance in parallel wires).



You say you have strange long runs between outlets and switches — if any of these extra lengths run in parallel, this is a great environment for the voltage from one to be induced in the other if it's disconnected.



If you try putting a load, like a small light bulb, across that 100 V, it will vanish (read 0 V), because there is no significant current capacity in this coupling. It might even go away if you were to attach an analog voltmeter (which is more of a load because current from the line to move the needle) instead of a digital one (which typically has a 1 MΩ input impedance that presents almost no load).






share|improve this answer
















However, if I only turn off the lights breaker, and go into the switch panel with my voltmeter, I am still detecting 100V AC across the switch (with it off), even though the lights stay off when I turn the switch on. … Can anyone tell me what might be going on?




Coupling between wires (inductance and capacitance in parallel wires).



You say you have strange long runs between outlets and switches — if any of these extra lengths run in parallel, this is a great environment for the voltage from one to be induced in the other if it's disconnected.



If you try putting a load, like a small light bulb, across that 100 V, it will vanish (read 0 V), because there is no significant current capacity in this coupling. It might even go away if you were to attach an analog voltmeter (which is more of a load because current from the line to move the needle) instead of a digital one (which typically has a 1 MΩ input impedance that presents almost no load).







share|improve this answer














share|improve this answer



share|improve this answer








edited yesterday

























answered yesterday









Kevin ReidKevin Reid

1,4691722




1,4691722








  • 3





    In other words - it's acting as an antenna.

    – J...
    yesterday











  • Note that even the induced voltage can still give you a noticeable electric shock, better not touch any wires where you are getting a 100 V reading.

    – user149408
    yesterday











  • It also could be due to a high resistance electrical connection between the wires.

    – Loren Pechtel
    yesterday














  • 3





    In other words - it's acting as an antenna.

    – J...
    yesterday











  • Note that even the induced voltage can still give you a noticeable electric shock, better not touch any wires where you are getting a 100 V reading.

    – user149408
    yesterday











  • It also could be due to a high resistance electrical connection between the wires.

    – Loren Pechtel
    yesterday








3




3





In other words - it's acting as an antenna.

– J...
yesterday





In other words - it's acting as an antenna.

– J...
yesterday













Note that even the induced voltage can still give you a noticeable electric shock, better not touch any wires where you are getting a 100 V reading.

– user149408
yesterday





Note that even the induced voltage can still give you a noticeable electric shock, better not touch any wires where you are getting a 100 V reading.

– user149408
yesterday













It also could be due to a high resistance electrical connection between the wires.

– Loren Pechtel
yesterday





It also could be due to a high resistance electrical connection between the wires.

– Loren Pechtel
yesterday













7














Rundown in layman's terms:




  1. Light switch to outlet. You will see a lot of these in older homes. By code for a long time in a lot of areas you had to be able to turn on a light from a switch accessible when entering a room. Easiest and most cost-effective way to do this is put switch to outlet. I had six rooms in my house like this.


  2. Dimmer to outlet. For sure not code compliant. You are correct that it could damage electronics and could be a huge fire/safety issue. Please replace this with a regular switch ASAP - $5 for a quick fix while you work things out.


  3. Dimmer to ceiling fan. Can't do this. If the ceiling fan has two hots coming into the box from fan you can buy a fan control + dimmer. If there is only one hot then you just install a switch and it is off/on for both.


  4. Light switches doing nothing. You must do a complete mapping assessment of your house. With a house like this it might take 3-6 hours. But you have to turn off one circuit at a time and figure out what doesn't work. You must also for 100% sure make sure that each switch is tested for working on every light and outlet (have a known working bulb). Write down every outlet and switch in a spreadsheet marking room, location, what it controls, and circuit.


  5. You cannot expect to plug LED bulbs into old dimmers and expect them to work. You need to put in a dimmer that is suitable for the type of LED you are installing.


  6. The dining room lights - need more info.







share|improve this answer


























  • There are three bedrooms with dimmer switches connected to outlets and fans. I am just replacing them all with toggle switches. There are only the two wires coming into the switch box, so no way I can use any fancier switches without heavy rewiring.

    – Joel Croteau
    yesterday
















7














Rundown in layman's terms:




  1. Light switch to outlet. You will see a lot of these in older homes. By code for a long time in a lot of areas you had to be able to turn on a light from a switch accessible when entering a room. Easiest and most cost-effective way to do this is put switch to outlet. I had six rooms in my house like this.


  2. Dimmer to outlet. For sure not code compliant. You are correct that it could damage electronics and could be a huge fire/safety issue. Please replace this with a regular switch ASAP - $5 for a quick fix while you work things out.


  3. Dimmer to ceiling fan. Can't do this. If the ceiling fan has two hots coming into the box from fan you can buy a fan control + dimmer. If there is only one hot then you just install a switch and it is off/on for both.


  4. Light switches doing nothing. You must do a complete mapping assessment of your house. With a house like this it might take 3-6 hours. But you have to turn off one circuit at a time and figure out what doesn't work. You must also for 100% sure make sure that each switch is tested for working on every light and outlet (have a known working bulb). Write down every outlet and switch in a spreadsheet marking room, location, what it controls, and circuit.


  5. You cannot expect to plug LED bulbs into old dimmers and expect them to work. You need to put in a dimmer that is suitable for the type of LED you are installing.


  6. The dining room lights - need more info.







share|improve this answer


























  • There are three bedrooms with dimmer switches connected to outlets and fans. I am just replacing them all with toggle switches. There are only the two wires coming into the switch box, so no way I can use any fancier switches without heavy rewiring.

    – Joel Croteau
    yesterday














7












7








7







Rundown in layman's terms:




  1. Light switch to outlet. You will see a lot of these in older homes. By code for a long time in a lot of areas you had to be able to turn on a light from a switch accessible when entering a room. Easiest and most cost-effective way to do this is put switch to outlet. I had six rooms in my house like this.


  2. Dimmer to outlet. For sure not code compliant. You are correct that it could damage electronics and could be a huge fire/safety issue. Please replace this with a regular switch ASAP - $5 for a quick fix while you work things out.


  3. Dimmer to ceiling fan. Can't do this. If the ceiling fan has two hots coming into the box from fan you can buy a fan control + dimmer. If there is only one hot then you just install a switch and it is off/on for both.


  4. Light switches doing nothing. You must do a complete mapping assessment of your house. With a house like this it might take 3-6 hours. But you have to turn off one circuit at a time and figure out what doesn't work. You must also for 100% sure make sure that each switch is tested for working on every light and outlet (have a known working bulb). Write down every outlet and switch in a spreadsheet marking room, location, what it controls, and circuit.


  5. You cannot expect to plug LED bulbs into old dimmers and expect them to work. You need to put in a dimmer that is suitable for the type of LED you are installing.


  6. The dining room lights - need more info.







share|improve this answer















Rundown in layman's terms:




  1. Light switch to outlet. You will see a lot of these in older homes. By code for a long time in a lot of areas you had to be able to turn on a light from a switch accessible when entering a room. Easiest and most cost-effective way to do this is put switch to outlet. I had six rooms in my house like this.


  2. Dimmer to outlet. For sure not code compliant. You are correct that it could damage electronics and could be a huge fire/safety issue. Please replace this with a regular switch ASAP - $5 for a quick fix while you work things out.


  3. Dimmer to ceiling fan. Can't do this. If the ceiling fan has two hots coming into the box from fan you can buy a fan control + dimmer. If there is only one hot then you just install a switch and it is off/on for both.


  4. Light switches doing nothing. You must do a complete mapping assessment of your house. With a house like this it might take 3-6 hours. But you have to turn off one circuit at a time and figure out what doesn't work. You must also for 100% sure make sure that each switch is tested for working on every light and outlet (have a known working bulb). Write down every outlet and switch in a spreadsheet marking room, location, what it controls, and circuit.


  5. You cannot expect to plug LED bulbs into old dimmers and expect them to work. You need to put in a dimmer that is suitable for the type of LED you are installing.


  6. The dining room lights - need more info.








share|improve this answer














share|improve this answer



share|improve this answer








edited yesterday









manassehkatz

9,8721337




9,8721337










answered yesterday









DMooreDMoore

28.6k1351120




28.6k1351120













  • There are three bedrooms with dimmer switches connected to outlets and fans. I am just replacing them all with toggle switches. There are only the two wires coming into the switch box, so no way I can use any fancier switches without heavy rewiring.

    – Joel Croteau
    yesterday



















  • There are three bedrooms with dimmer switches connected to outlets and fans. I am just replacing them all with toggle switches. There are only the two wires coming into the switch box, so no way I can use any fancier switches without heavy rewiring.

    – Joel Croteau
    yesterday

















There are three bedrooms with dimmer switches connected to outlets and fans. I am just replacing them all with toggle switches. There are only the two wires coming into the switch box, so no way I can use any fancier switches without heavy rewiring.

– Joel Croteau
yesterday





There are three bedrooms with dimmer switches connected to outlets and fans. I am just replacing them all with toggle switches. There are only the two wires coming into the switch box, so no way I can use any fancier switches without heavy rewiring.

– Joel Croteau
yesterday











6














Switch switching outlets. That's normal enough. Often the outlet(s) switched are far from the switch, because that is where the installer thought you would want to put the light. The installer was wrong. They always are. Because of that some of them switch more than one receptacle.



Split receptacles. That is normal. That's what the "tab" between the brass screws is for. Leave the tab on, the 2 screws are an easy way to splice. Break it off, you control each socket with a separate hot. There's also a tab on the neutral side if you want the sockets on 2 separate circuits.



Dimmers on receptacles. No no no! For the reasons you stated and worse. You know what to do. If you were super attached to dimmable receptacles, they make specially keyed receptacles just for lamps.



Mystery lamps. Fair possibility the bulbs are burnt out (back in the old days, bulbs burned out, true fact) or there is something wrong with the fixture. They make wire tracing devices if you really want to dive into the mysteries.



Mystery switches. Aside from that they may control a broken lamp, sometimes that just happens as wiring gets revised. They may also control receptacles that you have not checked, outside lights you do not see (optionally: with burned out bulbs) etc. They may also be half of a miswired 3-way circuit that is miswired in a way only the other switch works. **3-way switches do not have the words "on" or "off" on them.



Glowing LEDs on dimmers. Actually, the incandescents also glowed, but only in infrared, so you would have needed to be an elf to see it. LEDs are so much more efficient (and glow only in the visible range) that it's much more obvious. The reason is many switch loops do not have neutral wires. That means dimmers cannot power themselves between supply and neutral; they must place themselves in series with the lamps. That works slick on incandescents.



By the way, some dimmers actually have a "hard off" or even "hard on" setting. It's not in the smooth working range of the dimmer. You have to push the knob harder past a detent to reach that position. Most people, it never occurs to them to push it that hard, so they never know it's there. The "hard off" is important so you can change the bulb safely. The "hard on" is nice because it stops the bulb from buzzing. Dimmers aren't variacs, and their waveform is real sawtoothey.



Grouping of lamp circuits. It is common and wise for lamps to be powered from a different circuit than receptacles. That way if you trip a breaker you are not also in the pitch black. It is extremely unusual for lighting to trip a breaker (especially if LED), however they need to be provisioned with a worst case scenario (all oversized incandescents) in mind, and 125% of that.



Crosstalk. This is plain old capacitive coupling. Lay two wires alongside each other, one energized with AC, one disconencted, this will "antenna" some microscopic current onto the other wire. Cheap DVMs are so sensitive they can see this. Use a traditional analog voltmeter and that it will extinguish that phantom voltage; there's not enough current behind the phantom voltage to move the jeweled meter movement.



Multi-wire branch circuits (MWBC). This is a pair of half-circuits wired using a common neutral. The two half-circuits must be 240V across the hots, with neutral in the middle. That way the neutral carries the difference in currents, and you can trust it won't exceed breaker value. Done wrong, neutral carries the sum of currents, which overloads it!



In any circuit, all wires must be carried in the same cable or conduit so currents in each direction cancel each other out. This is AC power: any gap will induce vibration and fatigue failure. All that is relevant because the phantom-voltage wire may well be half of an MWBC, which would explain the strong capacitive coupling.



There are additional rules with MWBCs. Neutrals must be pigtailed, not use a device like a receptacle as a splice point. The breakers must be handle-tied so they shut off together, but normally a 2-pole breaker is used.



I expect your double circuit (the one with the phantom voltage) is a MWBC, and the work was done back before handle ties were required.



MWBCs have fallen out of favor because they are difficult to use with AFCI or GFCI protection, which is now required on almost all circuits.






share|improve this answer


























  • Nerd disclaimer. "you would have needed to be an elf or halfling to see it"; halflings, while perceptive, sneaky, sure-footed, and good with thrown missiles, are not known for extraordinary vision like elves are.

    – Jimmy Fix-it
    yesterday











  • @JimmyFix-it The trait I was thinking of is infravision, or "not needing to buy a FLIR". It's been a long time but I thought I recalled in D&D lore, pretty much everyone but humans seems to have it lol.

    – Harper
    yesterday






  • 2





    you are so right. In Gygax's original AD&D they did have infravision. In subsequent iterations, alas, the doughty halflings seem to have lost this trait...

    – Jimmy Fix-it
    yesterday











  • @harper re the original dining room dimmer switch, it actually had a detente at the bottom of the switch range, but even below that, the lights were still glowing. If I pushed down on the switch when it was at the bottom of Its range, I could force the lights off, but as soon as I took my finger off, they would come back on. That's why I said I thought it was a faulty switch.

    – Joel Croteau
    21 hours ago
















6














Switch switching outlets. That's normal enough. Often the outlet(s) switched are far from the switch, because that is where the installer thought you would want to put the light. The installer was wrong. They always are. Because of that some of them switch more than one receptacle.



Split receptacles. That is normal. That's what the "tab" between the brass screws is for. Leave the tab on, the 2 screws are an easy way to splice. Break it off, you control each socket with a separate hot. There's also a tab on the neutral side if you want the sockets on 2 separate circuits.



Dimmers on receptacles. No no no! For the reasons you stated and worse. You know what to do. If you were super attached to dimmable receptacles, they make specially keyed receptacles just for lamps.



Mystery lamps. Fair possibility the bulbs are burnt out (back in the old days, bulbs burned out, true fact) or there is something wrong with the fixture. They make wire tracing devices if you really want to dive into the mysteries.



Mystery switches. Aside from that they may control a broken lamp, sometimes that just happens as wiring gets revised. They may also control receptacles that you have not checked, outside lights you do not see (optionally: with burned out bulbs) etc. They may also be half of a miswired 3-way circuit that is miswired in a way only the other switch works. **3-way switches do not have the words "on" or "off" on them.



Glowing LEDs on dimmers. Actually, the incandescents also glowed, but only in infrared, so you would have needed to be an elf to see it. LEDs are so much more efficient (and glow only in the visible range) that it's much more obvious. The reason is many switch loops do not have neutral wires. That means dimmers cannot power themselves between supply and neutral; they must place themselves in series with the lamps. That works slick on incandescents.



By the way, some dimmers actually have a "hard off" or even "hard on" setting. It's not in the smooth working range of the dimmer. You have to push the knob harder past a detent to reach that position. Most people, it never occurs to them to push it that hard, so they never know it's there. The "hard off" is important so you can change the bulb safely. The "hard on" is nice because it stops the bulb from buzzing. Dimmers aren't variacs, and their waveform is real sawtoothey.



Grouping of lamp circuits. It is common and wise for lamps to be powered from a different circuit than receptacles. That way if you trip a breaker you are not also in the pitch black. It is extremely unusual for lighting to trip a breaker (especially if LED), however they need to be provisioned with a worst case scenario (all oversized incandescents) in mind, and 125% of that.



Crosstalk. This is plain old capacitive coupling. Lay two wires alongside each other, one energized with AC, one disconencted, this will "antenna" some microscopic current onto the other wire. Cheap DVMs are so sensitive they can see this. Use a traditional analog voltmeter and that it will extinguish that phantom voltage; there's not enough current behind the phantom voltage to move the jeweled meter movement.



Multi-wire branch circuits (MWBC). This is a pair of half-circuits wired using a common neutral. The two half-circuits must be 240V across the hots, with neutral in the middle. That way the neutral carries the difference in currents, and you can trust it won't exceed breaker value. Done wrong, neutral carries the sum of currents, which overloads it!



In any circuit, all wires must be carried in the same cable or conduit so currents in each direction cancel each other out. This is AC power: any gap will induce vibration and fatigue failure. All that is relevant because the phantom-voltage wire may well be half of an MWBC, which would explain the strong capacitive coupling.



There are additional rules with MWBCs. Neutrals must be pigtailed, not use a device like a receptacle as a splice point. The breakers must be handle-tied so they shut off together, but normally a 2-pole breaker is used.



I expect your double circuit (the one with the phantom voltage) is a MWBC, and the work was done back before handle ties were required.



MWBCs have fallen out of favor because they are difficult to use with AFCI or GFCI protection, which is now required on almost all circuits.






share|improve this answer


























  • Nerd disclaimer. "you would have needed to be an elf or halfling to see it"; halflings, while perceptive, sneaky, sure-footed, and good with thrown missiles, are not known for extraordinary vision like elves are.

    – Jimmy Fix-it
    yesterday











  • @JimmyFix-it The trait I was thinking of is infravision, or "not needing to buy a FLIR". It's been a long time but I thought I recalled in D&D lore, pretty much everyone but humans seems to have it lol.

    – Harper
    yesterday






  • 2





    you are so right. In Gygax's original AD&D they did have infravision. In subsequent iterations, alas, the doughty halflings seem to have lost this trait...

    – Jimmy Fix-it
    yesterday











  • @harper re the original dining room dimmer switch, it actually had a detente at the bottom of the switch range, but even below that, the lights were still glowing. If I pushed down on the switch when it was at the bottom of Its range, I could force the lights off, but as soon as I took my finger off, they would come back on. That's why I said I thought it was a faulty switch.

    – Joel Croteau
    21 hours ago














6












6








6







Switch switching outlets. That's normal enough. Often the outlet(s) switched are far from the switch, because that is where the installer thought you would want to put the light. The installer was wrong. They always are. Because of that some of them switch more than one receptacle.



Split receptacles. That is normal. That's what the "tab" between the brass screws is for. Leave the tab on, the 2 screws are an easy way to splice. Break it off, you control each socket with a separate hot. There's also a tab on the neutral side if you want the sockets on 2 separate circuits.



Dimmers on receptacles. No no no! For the reasons you stated and worse. You know what to do. If you were super attached to dimmable receptacles, they make specially keyed receptacles just for lamps.



Mystery lamps. Fair possibility the bulbs are burnt out (back in the old days, bulbs burned out, true fact) or there is something wrong with the fixture. They make wire tracing devices if you really want to dive into the mysteries.



Mystery switches. Aside from that they may control a broken lamp, sometimes that just happens as wiring gets revised. They may also control receptacles that you have not checked, outside lights you do not see (optionally: with burned out bulbs) etc. They may also be half of a miswired 3-way circuit that is miswired in a way only the other switch works. **3-way switches do not have the words "on" or "off" on them.



Glowing LEDs on dimmers. Actually, the incandescents also glowed, but only in infrared, so you would have needed to be an elf to see it. LEDs are so much more efficient (and glow only in the visible range) that it's much more obvious. The reason is many switch loops do not have neutral wires. That means dimmers cannot power themselves between supply and neutral; they must place themselves in series with the lamps. That works slick on incandescents.



By the way, some dimmers actually have a "hard off" or even "hard on" setting. It's not in the smooth working range of the dimmer. You have to push the knob harder past a detent to reach that position. Most people, it never occurs to them to push it that hard, so they never know it's there. The "hard off" is important so you can change the bulb safely. The "hard on" is nice because it stops the bulb from buzzing. Dimmers aren't variacs, and their waveform is real sawtoothey.



Grouping of lamp circuits. It is common and wise for lamps to be powered from a different circuit than receptacles. That way if you trip a breaker you are not also in the pitch black. It is extremely unusual for lighting to trip a breaker (especially if LED), however they need to be provisioned with a worst case scenario (all oversized incandescents) in mind, and 125% of that.



Crosstalk. This is plain old capacitive coupling. Lay two wires alongside each other, one energized with AC, one disconencted, this will "antenna" some microscopic current onto the other wire. Cheap DVMs are so sensitive they can see this. Use a traditional analog voltmeter and that it will extinguish that phantom voltage; there's not enough current behind the phantom voltage to move the jeweled meter movement.



Multi-wire branch circuits (MWBC). This is a pair of half-circuits wired using a common neutral. The two half-circuits must be 240V across the hots, with neutral in the middle. That way the neutral carries the difference in currents, and you can trust it won't exceed breaker value. Done wrong, neutral carries the sum of currents, which overloads it!



In any circuit, all wires must be carried in the same cable or conduit so currents in each direction cancel each other out. This is AC power: any gap will induce vibration and fatigue failure. All that is relevant because the phantom-voltage wire may well be half of an MWBC, which would explain the strong capacitive coupling.



There are additional rules with MWBCs. Neutrals must be pigtailed, not use a device like a receptacle as a splice point. The breakers must be handle-tied so they shut off together, but normally a 2-pole breaker is used.



I expect your double circuit (the one with the phantom voltage) is a MWBC, and the work was done back before handle ties were required.



MWBCs have fallen out of favor because they are difficult to use with AFCI or GFCI protection, which is now required on almost all circuits.






share|improve this answer















Switch switching outlets. That's normal enough. Often the outlet(s) switched are far from the switch, because that is where the installer thought you would want to put the light. The installer was wrong. They always are. Because of that some of them switch more than one receptacle.



Split receptacles. That is normal. That's what the "tab" between the brass screws is for. Leave the tab on, the 2 screws are an easy way to splice. Break it off, you control each socket with a separate hot. There's also a tab on the neutral side if you want the sockets on 2 separate circuits.



Dimmers on receptacles. No no no! For the reasons you stated and worse. You know what to do. If you were super attached to dimmable receptacles, they make specially keyed receptacles just for lamps.



Mystery lamps. Fair possibility the bulbs are burnt out (back in the old days, bulbs burned out, true fact) or there is something wrong with the fixture. They make wire tracing devices if you really want to dive into the mysteries.



Mystery switches. Aside from that they may control a broken lamp, sometimes that just happens as wiring gets revised. They may also control receptacles that you have not checked, outside lights you do not see (optionally: with burned out bulbs) etc. They may also be half of a miswired 3-way circuit that is miswired in a way only the other switch works. **3-way switches do not have the words "on" or "off" on them.



Glowing LEDs on dimmers. Actually, the incandescents also glowed, but only in infrared, so you would have needed to be an elf to see it. LEDs are so much more efficient (and glow only in the visible range) that it's much more obvious. The reason is many switch loops do not have neutral wires. That means dimmers cannot power themselves between supply and neutral; they must place themselves in series with the lamps. That works slick on incandescents.



By the way, some dimmers actually have a "hard off" or even "hard on" setting. It's not in the smooth working range of the dimmer. You have to push the knob harder past a detent to reach that position. Most people, it never occurs to them to push it that hard, so they never know it's there. The "hard off" is important so you can change the bulb safely. The "hard on" is nice because it stops the bulb from buzzing. Dimmers aren't variacs, and their waveform is real sawtoothey.



Grouping of lamp circuits. It is common and wise for lamps to be powered from a different circuit than receptacles. That way if you trip a breaker you are not also in the pitch black. It is extremely unusual for lighting to trip a breaker (especially if LED), however they need to be provisioned with a worst case scenario (all oversized incandescents) in mind, and 125% of that.



Crosstalk. This is plain old capacitive coupling. Lay two wires alongside each other, one energized with AC, one disconencted, this will "antenna" some microscopic current onto the other wire. Cheap DVMs are so sensitive they can see this. Use a traditional analog voltmeter and that it will extinguish that phantom voltage; there's not enough current behind the phantom voltage to move the jeweled meter movement.



Multi-wire branch circuits (MWBC). This is a pair of half-circuits wired using a common neutral. The two half-circuits must be 240V across the hots, with neutral in the middle. That way the neutral carries the difference in currents, and you can trust it won't exceed breaker value. Done wrong, neutral carries the sum of currents, which overloads it!



In any circuit, all wires must be carried in the same cable or conduit so currents in each direction cancel each other out. This is AC power: any gap will induce vibration and fatigue failure. All that is relevant because the phantom-voltage wire may well be half of an MWBC, which would explain the strong capacitive coupling.



There are additional rules with MWBCs. Neutrals must be pigtailed, not use a device like a receptacle as a splice point. The breakers must be handle-tied so they shut off together, but normally a 2-pole breaker is used.



I expect your double circuit (the one with the phantom voltage) is a MWBC, and the work was done back before handle ties were required.



MWBCs have fallen out of favor because they are difficult to use with AFCI or GFCI protection, which is now required on almost all circuits.







share|improve this answer














share|improve this answer



share|improve this answer








edited yesterday

























answered yesterday









HarperHarper

74.4k448149




74.4k448149













  • Nerd disclaimer. "you would have needed to be an elf or halfling to see it"; halflings, while perceptive, sneaky, sure-footed, and good with thrown missiles, are not known for extraordinary vision like elves are.

    – Jimmy Fix-it
    yesterday











  • @JimmyFix-it The trait I was thinking of is infravision, or "not needing to buy a FLIR". It's been a long time but I thought I recalled in D&D lore, pretty much everyone but humans seems to have it lol.

    – Harper
    yesterday






  • 2





    you are so right. In Gygax's original AD&D they did have infravision. In subsequent iterations, alas, the doughty halflings seem to have lost this trait...

    – Jimmy Fix-it
    yesterday











  • @harper re the original dining room dimmer switch, it actually had a detente at the bottom of the switch range, but even below that, the lights were still glowing. If I pushed down on the switch when it was at the bottom of Its range, I could force the lights off, but as soon as I took my finger off, they would come back on. That's why I said I thought it was a faulty switch.

    – Joel Croteau
    21 hours ago



















  • Nerd disclaimer. "you would have needed to be an elf or halfling to see it"; halflings, while perceptive, sneaky, sure-footed, and good with thrown missiles, are not known for extraordinary vision like elves are.

    – Jimmy Fix-it
    yesterday











  • @JimmyFix-it The trait I was thinking of is infravision, or "not needing to buy a FLIR". It's been a long time but I thought I recalled in D&D lore, pretty much everyone but humans seems to have it lol.

    – Harper
    yesterday






  • 2





    you are so right. In Gygax's original AD&D they did have infravision. In subsequent iterations, alas, the doughty halflings seem to have lost this trait...

    – Jimmy Fix-it
    yesterday











  • @harper re the original dining room dimmer switch, it actually had a detente at the bottom of the switch range, but even below that, the lights were still glowing. If I pushed down on the switch when it was at the bottom of Its range, I could force the lights off, but as soon as I took my finger off, they would come back on. That's why I said I thought it was a faulty switch.

    – Joel Croteau
    21 hours ago

















Nerd disclaimer. "you would have needed to be an elf or halfling to see it"; halflings, while perceptive, sneaky, sure-footed, and good with thrown missiles, are not known for extraordinary vision like elves are.

– Jimmy Fix-it
yesterday





Nerd disclaimer. "you would have needed to be an elf or halfling to see it"; halflings, while perceptive, sneaky, sure-footed, and good with thrown missiles, are not known for extraordinary vision like elves are.

– Jimmy Fix-it
yesterday













@JimmyFix-it The trait I was thinking of is infravision, or "not needing to buy a FLIR". It's been a long time but I thought I recalled in D&D lore, pretty much everyone but humans seems to have it lol.

– Harper
yesterday





@JimmyFix-it The trait I was thinking of is infravision, or "not needing to buy a FLIR". It's been a long time but I thought I recalled in D&D lore, pretty much everyone but humans seems to have it lol.

– Harper
yesterday




2




2





you are so right. In Gygax's original AD&D they did have infravision. In subsequent iterations, alas, the doughty halflings seem to have lost this trait...

– Jimmy Fix-it
yesterday





you are so right. In Gygax's original AD&D they did have infravision. In subsequent iterations, alas, the doughty halflings seem to have lost this trait...

– Jimmy Fix-it
yesterday













@harper re the original dining room dimmer switch, it actually had a detente at the bottom of the switch range, but even below that, the lights were still glowing. If I pushed down on the switch when it was at the bottom of Its range, I could force the lights off, but as soon as I took my finger off, they would come back on. That's why I said I thought it was a faulty switch.

– Joel Croteau
21 hours ago





@harper re the original dining room dimmer switch, it actually had a detente at the bottom of the switch range, but even below that, the lights were still glowing. If I pushed down on the switch when it was at the bottom of Its range, I could force the lights off, but as soon as I took my finger off, they would come back on. That's why I said I thought it was a faulty switch.

– Joel Croteau
21 hours ago










Joel Croteau is a new contributor. Be nice, and check out our Code of Conduct.










draft saved

draft discarded


















Joel Croteau is a new contributor. Be nice, and check out our Code of Conduct.













Joel Croteau is a new contributor. Be nice, and check out our Code of Conduct.












Joel Croteau is a new contributor. Be nice, and check out our Code of Conduct.
















Thanks for contributing an answer to Home Improvement Stack Exchange!


  • Please be sure to answer the question. Provide details and share your research!

But avoid



  • Asking for help, clarification, or responding to other answers.

  • Making statements based on opinion; back them up with references or personal experience.


To learn more, see our tips on writing great answers.




draft saved


draft discarded














StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f160497%2fcan-someone-explain-how-this-makes-sense-electrically%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown





















































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown

































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown







Popular posts from this blog

Færeyskur hestur Heimild | Tengill | Tilvísanir | LeiðsagnarvalRossið - síða um færeyska hrossið á færeyskuGott ár hjá færeyska hestinum

He _____ here since 1970 . Answer needed [closed]What does “since he was so high” mean?Meaning of “catch birds for”?How do I ensure “since” takes the meaning I want?“Who cares here” meaningWhat does “right round toward” mean?the time tense (had now been detected)What does the phrase “ring around the roses” mean here?Correct usage of “visited upon”Meaning of “foiled rail sabotage bid”It was the third time I had gone to Rome or It is the third time I had been to Rome

Slayer Innehåll Historia | Stil, komposition och lyrik | Bandets betydelse och framgångar | Sidoprojekt och samarbeten | Kontroverser | Medlemmar | Utmärkelser och nomineringar | Turnéer och festivaler | Diskografi | Referenser | Externa länkar | Navigeringsmenywww.slayer.net”Metal Massacre vol. 1””Metal Massacre vol. 3””Metal Massacre Volume III””Show No Mercy””Haunting the Chapel””Live Undead””Hell Awaits””Reign in Blood””Reign in Blood””Gold & Platinum – Reign in Blood””Golden Gods Awards Winners”originalet”Kerrang! Hall Of Fame””Slayer Looks Back On 37-Year Career In New Video Series: Part Two””South of Heaven””Gold & Platinum – South of Heaven””Seasons in the Abyss””Gold & Platinum - Seasons in the Abyss””Divine Intervention””Divine Intervention - Release group by Slayer””Gold & Platinum - Divine Intervention””Live Intrusion””Undisputed Attitude””Abolish Government/Superficial Love””Release “Slatanic Slaughter: A Tribute to Slayer” by Various Artists””Diabolus in Musica””Soundtrack to the Apocalypse””God Hates Us All””Systematic - Relationships””War at the Warfield””Gold & Platinum - War at the Warfield””Soundtrack to the Apocalypse””Gold & Platinum - Still Reigning””Metallica, Slayer, Iron Mauden Among Winners At Metal Hammer Awards””Eternal Pyre””Eternal Pyre - Slayer release group””Eternal Pyre””Metal Storm Awards 2006””Kerrang! Hall Of Fame””Slayer Wins 'Best Metal' Grammy Award””Slayer Guitarist Jeff Hanneman Dies””Bullet-For My Valentine booed at Metal Hammer Golden Gods Awards””Unholy Aliance””The End Of Slayer?””Slayer: We Could Thrash Out Two More Albums If We're Fast Enough...””'The Unholy Alliance: Chapter III' UK Dates Added”originalet”Megadeth And Slayer To Co-Headline 'Canadian Carnage' Trek”originalet”World Painted Blood””Release “World Painted Blood” by Slayer””Metallica Heading To Cinemas””Slayer, Megadeth To Join Forces For 'European Carnage' Tour - Dec. 18, 2010”originalet”Slayer's Hanneman Contracts Acute Infection; Band To Bring In Guest Guitarist””Cannibal Corpse's Pat O'Brien Will Step In As Slayer's Guest Guitarist”originalet”Slayer’s Jeff Hanneman Dead at 49””Dave Lombardo Says He Made Only $67,000 In 2011 While Touring With Slayer””Slayer: We Do Not Agree With Dave Lombardo's Substance Or Timeline Of Events””Slayer Welcomes Drummer Paul Bostaph Back To The Fold””Slayer Hope to Unveil Never-Before-Heard Jeff Hanneman Material on Next Album””Slayer Debut New Song 'Implode' During Surprise Golden Gods Appearance””Release group Repentless by Slayer””Repentless - Slayer - Credits””Slayer””Metal Storm Awards 2015””Slayer - to release comic book "Repentless #1"””Slayer To Release 'Repentless' 6.66" Vinyl Box Set””BREAKING NEWS: Slayer Announce Farewell Tour””Slayer Recruit Lamb of God, Anthrax, Behemoth + Testament for Final Tour””Slayer lägger ner efter 37 år””Slayer Announces Second North American Leg Of 'Final' Tour””Final World Tour””Slayer Announces Final European Tour With Lamb of God, Anthrax And Obituary””Slayer To Tour Europe With Lamb of God, Anthrax And Obituary””Slayer To Play 'Last French Show Ever' At Next Year's Hellfst””Slayer's Final World Tour Will Extend Into 2019””Death Angel's Rob Cavestany On Slayer's 'Farewell' Tour: 'Some Of Us Could See This Coming'””Testament Has No Plans To Retire Anytime Soon, Says Chuck Billy””Anthrax's Scott Ian On Slayer's 'Farewell' Tour Plans: 'I Was Surprised And I Wasn't Surprised'””Slayer””Slayer's Morbid Schlock””Review/Rock; For Slayer, the Mania Is the Message””Slayer - Biography””Slayer - Reign In Blood”originalet”Dave Lombardo””An exclusive oral history of Slayer”originalet”Exclusive! Interview With Slayer Guitarist Jeff Hanneman”originalet”Thinking Out Loud: Slayer's Kerry King on hair metal, Satan and being polite””Slayer Lyrics””Slayer - Biography””Most influential artists for extreme metal music””Slayer - Reign in Blood””Slayer guitarist Jeff Hanneman dies aged 49””Slatanic Slaughter: A Tribute to Slayer””Gateway to Hell: A Tribute to Slayer””Covered In Blood””Slayer: The Origins of Thrash in San Francisco, CA.””Why They Rule - #6 Slayer”originalet”Guitar World's 100 Greatest Heavy Metal Guitarists Of All Time”originalet”The fans have spoken: Slayer comes out on top in readers' polls”originalet”Tribute to Jeff Hanneman (1964-2013)””Lamb Of God Frontman: We Sound Like A Slayer Rip-Off””BEHEMOTH Frontman Pays Tribute To SLAYER's JEFF HANNEMAN””Slayer, Hatebreed Doing Double Duty On This Year's Ozzfest””System of a Down””Lacuna Coil’s Andrea Ferro Talks Influences, Skateboarding, Band Origins + More””Slayer - Reign in Blood””Into The Lungs of Hell””Slayer rules - en utställning om fans””Slayer and Their Fans Slashed Through a No-Holds-Barred Night at Gas Monkey””Home””Slayer””Gold & Platinum - The Big 4 Live from Sofia, Bulgaria””Exclusive! Interview With Slayer Guitarist Kerry King””2008-02-23: Wiltern, Los Angeles, CA, USA””Slayer's Kerry King To Perform With Megadeth Tonight! - Oct. 21, 2010”originalet”Dave Lombardo - Biography”Slayer Case DismissedArkiveradUltimate Classic Rock: Slayer guitarist Jeff Hanneman dead at 49.”Slayer: "We could never do any thing like Some Kind Of Monster..."””Cannibal Corpse'S Pat O'Brien Will Step In As Slayer'S Guest Guitarist | The Official Slayer Site”originalet”Slayer Wins 'Best Metal' Grammy Award””Slayer Guitarist Jeff Hanneman Dies””Kerrang! Awards 2006 Blog: Kerrang! Hall Of Fame””Kerrang! Awards 2013: Kerrang! Legend”originalet”Metallica, Slayer, Iron Maien Among Winners At Metal Hammer Awards””Metal Hammer Golden Gods Awards””Bullet For My Valentine Booed At Metal Hammer Golden Gods Awards””Metal Storm Awards 2006””Metal Storm Awards 2015””Slayer's Concert History””Slayer - Relationships””Slayer - Releases”Slayers officiella webbplatsSlayer på MusicBrainzOfficiell webbplatsSlayerSlayerr1373445760000 0001 1540 47353068615-5086262726cb13906545x(data)6033143kn20030215029