Is this light switch installation safe and legal?





.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty{
margin-bottom:0;
}








20

















I did this wiring in my bonus room years ago, and now I'm wondering if it is in fact legal and safe. This is a built-in book case that I built and installed myself. The bookshelf went in over a light switch box, so I moved the light switches with the boxes and cables you see here. I've removed the plastic blank faceplate for the picture. When the faceplate is installed, the two cables come out over the top of the faceplate. The two cables enter the top rear of the box through a cable clamp which you can't see in this picture.



I'm happy to go back and do it right if this doesn't pass muster. I guess my main question is whether the exposed cables are okay.



This is all in North Carolina, US.



picture of wiring in built in bookshelf





Update: here's a pic of the wiring in the wiremold tracks, before snapping on the elbow covers. I had to do quite a bit of hacksawing and grinding to shorten the elbows so they would fit.
completed wiring before elbow covers



And here's the almost completed job.
almost completed job



Thanks to all for the help!










share|improve this question
























  • 4





    Is there anything that stops someone from shoving books into the exposed NM cables, thus pinching/crushing them? That's my prime concern with this setup....

    – ThreePhaseEel
    May 27 at 20:40






  • 20





    @RobertMoody What do those abbreviations mean?

    – Wilson
    May 28 at 7:34






  • 6





    @Wilson, they are types of wire. UF is "underground feeder" rated for direct burial (usually not used inside), and NM-B is "Non-metallic" and is the proper term for common residential wire known by its brand name, "Romex". Lastly, AHJ is "Authority Having Jurisdiction" which is a generic term for whatever city or county or state entity is responsible for inspecting electrical (or plumbing or whatever) work in the area.

    – JPhi1618
    May 28 at 17:45








  • 1





    Thanks @jphi1618. Turns out none of that applies in my country. Must be a US specific thing

    – Wilson
    May 28 at 19:05






  • 2





    @RobertMoody nah nah nah, (dodgey salesman voice) he's missing a GST which was suppossed to be connected to the SPE but it can't beacuse the XYZ and ABC wires are crossing with the WRE

    – Emobe
    May 29 at 7:01




















20

















I did this wiring in my bonus room years ago, and now I'm wondering if it is in fact legal and safe. This is a built-in book case that I built and installed myself. The bookshelf went in over a light switch box, so I moved the light switches with the boxes and cables you see here. I've removed the plastic blank faceplate for the picture. When the faceplate is installed, the two cables come out over the top of the faceplate. The two cables enter the top rear of the box through a cable clamp which you can't see in this picture.



I'm happy to go back and do it right if this doesn't pass muster. I guess my main question is whether the exposed cables are okay.



This is all in North Carolina, US.



picture of wiring in built in bookshelf





Update: here's a pic of the wiring in the wiremold tracks, before snapping on the elbow covers. I had to do quite a bit of hacksawing and grinding to shorten the elbows so they would fit.
completed wiring before elbow covers



And here's the almost completed job.
almost completed job



Thanks to all for the help!










share|improve this question
























  • 4





    Is there anything that stops someone from shoving books into the exposed NM cables, thus pinching/crushing them? That's my prime concern with this setup....

    – ThreePhaseEel
    May 27 at 20:40






  • 20





    @RobertMoody What do those abbreviations mean?

    – Wilson
    May 28 at 7:34






  • 6





    @Wilson, they are types of wire. UF is "underground feeder" rated for direct burial (usually not used inside), and NM-B is "Non-metallic" and is the proper term for common residential wire known by its brand name, "Romex". Lastly, AHJ is "Authority Having Jurisdiction" which is a generic term for whatever city or county or state entity is responsible for inspecting electrical (or plumbing or whatever) work in the area.

    – JPhi1618
    May 28 at 17:45








  • 1





    Thanks @jphi1618. Turns out none of that applies in my country. Must be a US specific thing

    – Wilson
    May 28 at 19:05






  • 2





    @RobertMoody nah nah nah, (dodgey salesman voice) he's missing a GST which was suppossed to be connected to the SPE but it can't beacuse the XYZ and ABC wires are crossing with the WRE

    – Emobe
    May 29 at 7:01
















20












20








20








I did this wiring in my bonus room years ago, and now I'm wondering if it is in fact legal and safe. This is a built-in book case that I built and installed myself. The bookshelf went in over a light switch box, so I moved the light switches with the boxes and cables you see here. I've removed the plastic blank faceplate for the picture. When the faceplate is installed, the two cables come out over the top of the faceplate. The two cables enter the top rear of the box through a cable clamp which you can't see in this picture.



I'm happy to go back and do it right if this doesn't pass muster. I guess my main question is whether the exposed cables are okay.



This is all in North Carolina, US.



picture of wiring in built in bookshelf





Update: here's a pic of the wiring in the wiremold tracks, before snapping on the elbow covers. I had to do quite a bit of hacksawing and grinding to shorten the elbows so they would fit.
completed wiring before elbow covers



And here's the almost completed job.
almost completed job



Thanks to all for the help!










share|improve this question
















I did this wiring in my bonus room years ago, and now I'm wondering if it is in fact legal and safe. This is a built-in book case that I built and installed myself. The bookshelf went in over a light switch box, so I moved the light switches with the boxes and cables you see here. I've removed the plastic blank faceplate for the picture. When the faceplate is installed, the two cables come out over the top of the faceplate. The two cables enter the top rear of the box through a cable clamp which you can't see in this picture.



I'm happy to go back and do it right if this doesn't pass muster. I guess my main question is whether the exposed cables are okay.



This is all in North Carolina, US.



picture of wiring in built in bookshelf





Update: here's a pic of the wiring in the wiremold tracks, before snapping on the elbow covers. I had to do quite a bit of hacksawing and grinding to shorten the elbows so they would fit.
completed wiring before elbow covers



And here's the almost completed job.
almost completed job



Thanks to all for the help!







electrical wiring






share|improve this question















share|improve this question













share|improve this question




share|improve this question



share|improve this question








edited Jun 3 at 3:17







TreyGuy

















asked May 27 at 20:32









TreyGuyTreyGuy

1031 gold badge1 silver badge6 bronze badges




1031 gold badge1 silver badge6 bronze badges











  • 4





    Is there anything that stops someone from shoving books into the exposed NM cables, thus pinching/crushing them? That's my prime concern with this setup....

    – ThreePhaseEel
    May 27 at 20:40






  • 20





    @RobertMoody What do those abbreviations mean?

    – Wilson
    May 28 at 7:34






  • 6





    @Wilson, they are types of wire. UF is "underground feeder" rated for direct burial (usually not used inside), and NM-B is "Non-metallic" and is the proper term for common residential wire known by its brand name, "Romex". Lastly, AHJ is "Authority Having Jurisdiction" which is a generic term for whatever city or county or state entity is responsible for inspecting electrical (or plumbing or whatever) work in the area.

    – JPhi1618
    May 28 at 17:45








  • 1





    Thanks @jphi1618. Turns out none of that applies in my country. Must be a US specific thing

    – Wilson
    May 28 at 19:05






  • 2





    @RobertMoody nah nah nah, (dodgey salesman voice) he's missing a GST which was suppossed to be connected to the SPE but it can't beacuse the XYZ and ABC wires are crossing with the WRE

    – Emobe
    May 29 at 7:01
















  • 4





    Is there anything that stops someone from shoving books into the exposed NM cables, thus pinching/crushing them? That's my prime concern with this setup....

    – ThreePhaseEel
    May 27 at 20:40






  • 20





    @RobertMoody What do those abbreviations mean?

    – Wilson
    May 28 at 7:34






  • 6





    @Wilson, they are types of wire. UF is "underground feeder" rated for direct burial (usually not used inside), and NM-B is "Non-metallic" and is the proper term for common residential wire known by its brand name, "Romex". Lastly, AHJ is "Authority Having Jurisdiction" which is a generic term for whatever city or county or state entity is responsible for inspecting electrical (or plumbing or whatever) work in the area.

    – JPhi1618
    May 28 at 17:45








  • 1





    Thanks @jphi1618. Turns out none of that applies in my country. Must be a US specific thing

    – Wilson
    May 28 at 19:05






  • 2





    @RobertMoody nah nah nah, (dodgey salesman voice) he's missing a GST which was suppossed to be connected to the SPE but it can't beacuse the XYZ and ABC wires are crossing with the WRE

    – Emobe
    May 29 at 7:01










4




4





Is there anything that stops someone from shoving books into the exposed NM cables, thus pinching/crushing them? That's my prime concern with this setup....

– ThreePhaseEel
May 27 at 20:40





Is there anything that stops someone from shoving books into the exposed NM cables, thus pinching/crushing them? That's my prime concern with this setup....

– ThreePhaseEel
May 27 at 20:40




20




20





@RobertMoody What do those abbreviations mean?

– Wilson
May 28 at 7:34





@RobertMoody What do those abbreviations mean?

– Wilson
May 28 at 7:34




6




6





@Wilson, they are types of wire. UF is "underground feeder" rated for direct burial (usually not used inside), and NM-B is "Non-metallic" and is the proper term for common residential wire known by its brand name, "Romex". Lastly, AHJ is "Authority Having Jurisdiction" which is a generic term for whatever city or county or state entity is responsible for inspecting electrical (or plumbing or whatever) work in the area.

– JPhi1618
May 28 at 17:45







@Wilson, they are types of wire. UF is "underground feeder" rated for direct burial (usually not used inside), and NM-B is "Non-metallic" and is the proper term for common residential wire known by its brand name, "Romex". Lastly, AHJ is "Authority Having Jurisdiction" which is a generic term for whatever city or county or state entity is responsible for inspecting electrical (or plumbing or whatever) work in the area.

– JPhi1618
May 28 at 17:45






1




1





Thanks @jphi1618. Turns out none of that applies in my country. Must be a US specific thing

– Wilson
May 28 at 19:05





Thanks @jphi1618. Turns out none of that applies in my country. Must be a US specific thing

– Wilson
May 28 at 19:05




2




2





@RobertMoody nah nah nah, (dodgey salesman voice) he's missing a GST which was suppossed to be connected to the SPE but it can't beacuse the XYZ and ABC wires are crossing with the WRE

– Emobe
May 29 at 7:01







@RobertMoody nah nah nah, (dodgey salesman voice) he's missing a GST which was suppossed to be connected to the SPE but it can't beacuse the XYZ and ABC wires are crossing with the WRE

– Emobe
May 29 at 7:01












6 Answers
6






active

oldest

votes


















27


















My concern here would be for physical abuse



Right now, nothing stops those NM cables from getting whacked/pinched/crushed with books and such, especially if you have heavy tomes on your shelves. This could be considered a violation of NEC 334.15(A) or (B):




334.15 Exposed Work. In exposed work, except as provided
in 300.11(A), cable shall be installed as specified in 334.15(A)
through (C).



(A) To Follow Surface. Cable shall closely follow the surface
of the building finish or of running boards.



(B) Protection from Physical Damage. Cable shall be protected from physical damage where necessary by rigid metal
conduit, intermediate metal conduit, electrical metallic tubing,
Schedule 80 PVC conduit, Type RTRC marked with the suffix -XW, or other approved means. Where passing through a floor,
the cable shall be enclosed in rigid metal conduit, intermediate
metal conduit, electrical metallic tubing, Schedule 80 PVC
conduit, Type RTRC marked with the suffix -XW, or other
approved means extending at least 150 mm (6 in.) above the
floor.



Type NMC cable installed in shallow chases or grooves in
masonry, concrete, or adobe shall be protected in accordance
with the requirements in 300.4(F) and covered with plaster,
adobe, or similar finish.




You have two options to address this



There are two ways to address this issue: you can either replace the NM cables with a wiring method better suited to withstanding said reader-inflicted physical abuse, or you can put something in that will protect the boxes and cables from rough encounters with books while still allowing for access to them. We'll discuss these options in turn.



Making this more rugged



While the normal wiring methods that are used to withstand the NEC's definition of "physical damage" are the various flavors of heavy-duty rigid conduit (RMC, IMC, EMT, Schedule 80 PVC, and RTRC-XW), surface metal raceway is also rated for such a duty, and doesn't suffer from the bending radius issues that other wiring methods in this application would have to deal with.



If you're using Legrand's Wiremold line for this, you'll need:




  • Two BW17 right angle raceway-to-1/2" conduit fittings, attached with 1/2" chase nipples and locknuts

  • Two BWH6 flat elbows

  • A BWH7 inside elbow

  • A length of BWH1 raceway

  • And a two gang metal extension ring for the old switch box


The idea here is that you use the extension ring instead of the normal starter box (as they don't make one in two gang, and two-gang to one-gang mud rings stick out too far) along with one of the BW17 fittings and associated parts to get the raceway going upward from the gang furthest from the inside corner, then use the two flat elbows and the inside elbow to get around the bend and going back down. Then it's just a matter of using the other BW17 and its friends to transition the wires back into the box.



Once the raceway's in, then, you run individual THHN wires inside it to connect the circuits between the two boxes, just as if you were working in conduit. (The existing NM cables can be tossed, or shucked and their wires kept for pigtail duty, your choice.) Don't forget to plug the knockouts where the cables once entered/exited the boxes!



Using some cabinetry to box the boxes



If you feel yourself a better cabinetmaker than electrician, another option for this situation would be to put a cabinet divider wall in just to the right of this, and then add a cabinet door over the front, maintaining access while protecting the existing assembly from physical abuse or damage. This also has the advantage of being a more finished look, at the cost of having an "un-cabinet" in your house that you can't really use for anything at all. Making it match the existing built-in bookshelves may be a challenge, as well.






share|improve this answer






















  • 1





    Wow, thanks for the very detailed answer! Stay tuned for pics of the completed project.

    – TreyGuy
    May 27 at 23:40






  • 5





    @TreyGuy -- we upvote and/or accept folks' answers to show our thanks here :)

    – ThreePhaseEel
    May 27 at 23:41






  • 5





    @TreyGuy -- it's the greyed check below the vote arrows

    – ThreePhaseEel
    May 28 at 1:15






  • 1





    I do love the box it part..And as long as it is easy to get at splice laying there not nailed ..

    – user101687
    May 28 at 6:42






  • 7





    You can find/make fake book spines to cover up the lost space

    – ratchet freak
    May 28 at 11:04



















6


















I would go a different way here.



First, the original light switch junction box belongs in the actual wall, not pulled out into the cabinets which themselves could pull out of the wall. I would leave a nice big hole in the cabinet which aligns with the switch box.



They make blank steel cover plates for 2-gang boxes... They are fairly small dimensionally, and they have a 1/2" knockout on their face. I'd come out of that into flexible metal conduit, then the FMC into the back of that 2-gang handy-box you nicely installed.



I'd run 5 individual wires - stranded THHN will handle quite nicely, and one color will suffice since they're all hot (I recommend yellow since it takes colored sharpie well)... plus one green ground. Mark both ends with colored electrical tape or a Sharpie so you can distinguish them.



Wire nut them on to the matching wires inside the wall, send them through the tube, and mount the faceplate on the box that is in the actual wall. Then inside your new box, attach the THHN to switches. The ground goes to the ground screw on the handy-box and that's done. If you use stranded you must not use backstabs! Attaching to screws takes a knack; the best option is a "screw-to-clamp" type switch, where you tighten the screw to attach a back wire.






share|improve this answer



























  • I considered the FMC route, actually -- I felt that the surface metal raceway would offer better protection against damage for this, and I don't think built-in units are going to detach from the wall any time soon if at all adequately fitted...

    – ThreePhaseEel
    May 28 at 0:31






  • 1





    I've lived in earthquake country, built-ins anchored into drywall, that would not surprise me. I actually searched the NEMA plugs for an obscure but available xx-15 /3+gnd socket to make a way for it to plug in... But could not find a plug-socket set that was sanely priced.

    – Harper
    May 28 at 1:08








  • 2





    The cabinets are screwed to the studs, so I really don't think they're going anywhere.

    – TreyGuy
    May 28 at 1:10











  • @Harper -- yeah, the NEMA 14 line starts at 14-20 and goes up from there (and yeah, anchoring built-ins to drywall is a fool's errand in earthquake country IMO)

    – ThreePhaseEel
    May 28 at 1:17











  • Yes I was looking at NEMA 18, 20, odd stuff like 480 wye....That nobody would mistake for residential service...

    – Harper
    May 28 at 12:23



















3


















Another option would eminate the wiring altogether! Goconex (now Nevven) makes a wireless system that would give you all you space back. Two small controllers, actually small receiver/relay units, are wired into the circuits in the ganged box, the romex to the handy box pulled and discarded. The handy box can stay or not, as you wish, but if pulled a plain plate can cover the hole. Finally, two transmitter switches can be mounted in the same place as were the old switches. These appear to be standard Decora rocker switches, same mounting format, but have ZERO rear protrusion, can mount on a box or completely surface mounted. The entire switch unit fits behind a standard switchplate and is still flush with the wall. You can mount the switches anywhere within 100' (maybe you really never wanted them there?) Or add another switch? One switch can discriminately operate an infinite number of relays or one relay can be controlled by up to five switches.Batteries in the remote switches are said to last 10-15 yrs.






share|improve this answer



























  • I have this type of switch (although a different brand), and batteries only last around a year of bathroom type of use. They also use more expensive 12V batteries.

    – George Y.
    May 28 at 19:15











  • MK make a wireless battery-less switch which is piezo-powered. But it needs specialist receiver equipment and is quite expensive. This answer may be describing something similar for the US market.

    – Andrew Leach
    May 28 at 19:30











  • Great suggestion. Electricians don't usually think of, let alone consider, wireless solutions. (Errr, does "eminate" mean "eliminate"?)

    – wallyk
    May 29 at 16:46





















1


















I'm not sure why almost everyone is wanting to make your solution be expensive. Do a Google search for 2 gang electrical extension ring. Very simple to install. Keeps everything contained in your original wall box, but provides you the ability to extend the box into the bookcase.



Side note bookcase must be secured to the structure to be legal. Even though you didn't have to use the UF cable it can still be used in this application. You just turn OFF POWER, pull switches out, label wires with masking tape,( S1U, S1L,S2U, S-- switch, 1 or 2- left or right switch your choice, U,L- upper or lower power connection screws on the switches. Remove wires from the switches. Then remove the box that you used in the bookcase, get all wiring to come back into the original wall box. Use push plugs to close any holes in the wall box that are not being utilized for the incoming original wiring. Push all wiring back into original wall box to ensure safety of existing wire from damage, make sure hole in bookcase is aligned with original wall box, Install extension ring into hole in bookcase, push bookcase into place, attach extension ring to original wall box and then resecure bookcase to the structure, pull all wire back out through the extension ring, re-install wiring to the switches, add electrical tape around exterior of each switch, covering the power connection screws,. (Safety). Attach switches to extension ring, and reinstall wall plate. Ensure both switches are in the off position, turn power back on from source. Turn each switch on individually.



Everything should work as intended, but by turning each one on individually, if there is an issue, it will be easier to deduce if a problem exists. The most important thing to remember is to never work on a live circuit unless it is absolutely necessary. Any good electrical tradesman will express the same sentiments. We know how to work on live circuitry but try our best not to if possible. No reason to be another accident statistic when it's preventable. Leviton 42777-2WB is one example of an extension ring that could be used in this application






share|improve this answer
























  • 2





    Hello, and welcome to Home Improvement. This is interesting, but is hard to read as a long Wall 'O' Text. You might want to edit it to make it clearer; please take our tour so you'll know how better to contribute here.

    – Daniel Griscom
    May 29 at 14:19



















0


















Any exposed wire need to be covered or inclosed, wood box and slid it over the wires. I am more concerned with grounding in the metal box without a ground screw in the box you run the risk of electrocution.






share|improve this answer



























  • The box in back, at least, is likely grounded through the metal ground clip visible on the right side of the box.

    – ThreePhaseEel
    May 28 at 22:39



















0


















Use wire mold and come out of the top, go to the right, around the corner and back down. Drill a hole in the center of the faceplate (maybe get a metal faceplate if you need it) and use a 90° wiremold connector or use a 4" surface mount box (the kind that is made to use with wire mold) and come in to the top. Or do the same thing but with MC cable. You may need 12/3 or 12/4 depending on how many conductors you need. If it's just 1 switch you can use 12/2 and use the white as your switch leg but new code says you're not supposed to do that. You could always box in that corner but technically the "junction box" needs to be accessible. But if you're not getting an inspection then it's up to you. Ground those metal boxes!






share|improve this answer





























  • It looks like the box in back is grounded via the grounding clip visible on the right side of the box...

    – ThreePhaseEel
    May 28 at 22:18













Your Answer








StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "73"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);

StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});

function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/4.0/"u003ecc by-sa 4.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});


}
});















draft saved

draft discarded
















StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f166001%2fis-this-light-switch-installation-safe-and-legal%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown


























6 Answers
6






active

oldest

votes








6 Answers
6






active

oldest

votes









active

oldest

votes






active

oldest

votes









27


















My concern here would be for physical abuse



Right now, nothing stops those NM cables from getting whacked/pinched/crushed with books and such, especially if you have heavy tomes on your shelves. This could be considered a violation of NEC 334.15(A) or (B):




334.15 Exposed Work. In exposed work, except as provided
in 300.11(A), cable shall be installed as specified in 334.15(A)
through (C).



(A) To Follow Surface. Cable shall closely follow the surface
of the building finish or of running boards.



(B) Protection from Physical Damage. Cable shall be protected from physical damage where necessary by rigid metal
conduit, intermediate metal conduit, electrical metallic tubing,
Schedule 80 PVC conduit, Type RTRC marked with the suffix -XW, or other approved means. Where passing through a floor,
the cable shall be enclosed in rigid metal conduit, intermediate
metal conduit, electrical metallic tubing, Schedule 80 PVC
conduit, Type RTRC marked with the suffix -XW, or other
approved means extending at least 150 mm (6 in.) above the
floor.



Type NMC cable installed in shallow chases or grooves in
masonry, concrete, or adobe shall be protected in accordance
with the requirements in 300.4(F) and covered with plaster,
adobe, or similar finish.




You have two options to address this



There are two ways to address this issue: you can either replace the NM cables with a wiring method better suited to withstanding said reader-inflicted physical abuse, or you can put something in that will protect the boxes and cables from rough encounters with books while still allowing for access to them. We'll discuss these options in turn.



Making this more rugged



While the normal wiring methods that are used to withstand the NEC's definition of "physical damage" are the various flavors of heavy-duty rigid conduit (RMC, IMC, EMT, Schedule 80 PVC, and RTRC-XW), surface metal raceway is also rated for such a duty, and doesn't suffer from the bending radius issues that other wiring methods in this application would have to deal with.



If you're using Legrand's Wiremold line for this, you'll need:




  • Two BW17 right angle raceway-to-1/2" conduit fittings, attached with 1/2" chase nipples and locknuts

  • Two BWH6 flat elbows

  • A BWH7 inside elbow

  • A length of BWH1 raceway

  • And a two gang metal extension ring for the old switch box


The idea here is that you use the extension ring instead of the normal starter box (as they don't make one in two gang, and two-gang to one-gang mud rings stick out too far) along with one of the BW17 fittings and associated parts to get the raceway going upward from the gang furthest from the inside corner, then use the two flat elbows and the inside elbow to get around the bend and going back down. Then it's just a matter of using the other BW17 and its friends to transition the wires back into the box.



Once the raceway's in, then, you run individual THHN wires inside it to connect the circuits between the two boxes, just as if you were working in conduit. (The existing NM cables can be tossed, or shucked and their wires kept for pigtail duty, your choice.) Don't forget to plug the knockouts where the cables once entered/exited the boxes!



Using some cabinetry to box the boxes



If you feel yourself a better cabinetmaker than electrician, another option for this situation would be to put a cabinet divider wall in just to the right of this, and then add a cabinet door over the front, maintaining access while protecting the existing assembly from physical abuse or damage. This also has the advantage of being a more finished look, at the cost of having an "un-cabinet" in your house that you can't really use for anything at all. Making it match the existing built-in bookshelves may be a challenge, as well.






share|improve this answer






















  • 1





    Wow, thanks for the very detailed answer! Stay tuned for pics of the completed project.

    – TreyGuy
    May 27 at 23:40






  • 5





    @TreyGuy -- we upvote and/or accept folks' answers to show our thanks here :)

    – ThreePhaseEel
    May 27 at 23:41






  • 5





    @TreyGuy -- it's the greyed check below the vote arrows

    – ThreePhaseEel
    May 28 at 1:15






  • 1





    I do love the box it part..And as long as it is easy to get at splice laying there not nailed ..

    – user101687
    May 28 at 6:42






  • 7





    You can find/make fake book spines to cover up the lost space

    – ratchet freak
    May 28 at 11:04
















27


















My concern here would be for physical abuse



Right now, nothing stops those NM cables from getting whacked/pinched/crushed with books and such, especially if you have heavy tomes on your shelves. This could be considered a violation of NEC 334.15(A) or (B):




334.15 Exposed Work. In exposed work, except as provided
in 300.11(A), cable shall be installed as specified in 334.15(A)
through (C).



(A) To Follow Surface. Cable shall closely follow the surface
of the building finish or of running boards.



(B) Protection from Physical Damage. Cable shall be protected from physical damage where necessary by rigid metal
conduit, intermediate metal conduit, electrical metallic tubing,
Schedule 80 PVC conduit, Type RTRC marked with the suffix -XW, or other approved means. Where passing through a floor,
the cable shall be enclosed in rigid metal conduit, intermediate
metal conduit, electrical metallic tubing, Schedule 80 PVC
conduit, Type RTRC marked with the suffix -XW, or other
approved means extending at least 150 mm (6 in.) above the
floor.



Type NMC cable installed in shallow chases or grooves in
masonry, concrete, or adobe shall be protected in accordance
with the requirements in 300.4(F) and covered with plaster,
adobe, or similar finish.




You have two options to address this



There are two ways to address this issue: you can either replace the NM cables with a wiring method better suited to withstanding said reader-inflicted physical abuse, or you can put something in that will protect the boxes and cables from rough encounters with books while still allowing for access to them. We'll discuss these options in turn.



Making this more rugged



While the normal wiring methods that are used to withstand the NEC's definition of "physical damage" are the various flavors of heavy-duty rigid conduit (RMC, IMC, EMT, Schedule 80 PVC, and RTRC-XW), surface metal raceway is also rated for such a duty, and doesn't suffer from the bending radius issues that other wiring methods in this application would have to deal with.



If you're using Legrand's Wiremold line for this, you'll need:




  • Two BW17 right angle raceway-to-1/2" conduit fittings, attached with 1/2" chase nipples and locknuts

  • Two BWH6 flat elbows

  • A BWH7 inside elbow

  • A length of BWH1 raceway

  • And a two gang metal extension ring for the old switch box


The idea here is that you use the extension ring instead of the normal starter box (as they don't make one in two gang, and two-gang to one-gang mud rings stick out too far) along with one of the BW17 fittings and associated parts to get the raceway going upward from the gang furthest from the inside corner, then use the two flat elbows and the inside elbow to get around the bend and going back down. Then it's just a matter of using the other BW17 and its friends to transition the wires back into the box.



Once the raceway's in, then, you run individual THHN wires inside it to connect the circuits between the two boxes, just as if you were working in conduit. (The existing NM cables can be tossed, or shucked and their wires kept for pigtail duty, your choice.) Don't forget to plug the knockouts where the cables once entered/exited the boxes!



Using some cabinetry to box the boxes



If you feel yourself a better cabinetmaker than electrician, another option for this situation would be to put a cabinet divider wall in just to the right of this, and then add a cabinet door over the front, maintaining access while protecting the existing assembly from physical abuse or damage. This also has the advantage of being a more finished look, at the cost of having an "un-cabinet" in your house that you can't really use for anything at all. Making it match the existing built-in bookshelves may be a challenge, as well.






share|improve this answer






















  • 1





    Wow, thanks for the very detailed answer! Stay tuned for pics of the completed project.

    – TreyGuy
    May 27 at 23:40






  • 5





    @TreyGuy -- we upvote and/or accept folks' answers to show our thanks here :)

    – ThreePhaseEel
    May 27 at 23:41






  • 5





    @TreyGuy -- it's the greyed check below the vote arrows

    – ThreePhaseEel
    May 28 at 1:15






  • 1





    I do love the box it part..And as long as it is easy to get at splice laying there not nailed ..

    – user101687
    May 28 at 6:42






  • 7





    You can find/make fake book spines to cover up the lost space

    – ratchet freak
    May 28 at 11:04














27














27










27









My concern here would be for physical abuse



Right now, nothing stops those NM cables from getting whacked/pinched/crushed with books and such, especially if you have heavy tomes on your shelves. This could be considered a violation of NEC 334.15(A) or (B):




334.15 Exposed Work. In exposed work, except as provided
in 300.11(A), cable shall be installed as specified in 334.15(A)
through (C).



(A) To Follow Surface. Cable shall closely follow the surface
of the building finish or of running boards.



(B) Protection from Physical Damage. Cable shall be protected from physical damage where necessary by rigid metal
conduit, intermediate metal conduit, electrical metallic tubing,
Schedule 80 PVC conduit, Type RTRC marked with the suffix -XW, or other approved means. Where passing through a floor,
the cable shall be enclosed in rigid metal conduit, intermediate
metal conduit, electrical metallic tubing, Schedule 80 PVC
conduit, Type RTRC marked with the suffix -XW, or other
approved means extending at least 150 mm (6 in.) above the
floor.



Type NMC cable installed in shallow chases or grooves in
masonry, concrete, or adobe shall be protected in accordance
with the requirements in 300.4(F) and covered with plaster,
adobe, or similar finish.




You have two options to address this



There are two ways to address this issue: you can either replace the NM cables with a wiring method better suited to withstanding said reader-inflicted physical abuse, or you can put something in that will protect the boxes and cables from rough encounters with books while still allowing for access to them. We'll discuss these options in turn.



Making this more rugged



While the normal wiring methods that are used to withstand the NEC's definition of "physical damage" are the various flavors of heavy-duty rigid conduit (RMC, IMC, EMT, Schedule 80 PVC, and RTRC-XW), surface metal raceway is also rated for such a duty, and doesn't suffer from the bending radius issues that other wiring methods in this application would have to deal with.



If you're using Legrand's Wiremold line for this, you'll need:




  • Two BW17 right angle raceway-to-1/2" conduit fittings, attached with 1/2" chase nipples and locknuts

  • Two BWH6 flat elbows

  • A BWH7 inside elbow

  • A length of BWH1 raceway

  • And a two gang metal extension ring for the old switch box


The idea here is that you use the extension ring instead of the normal starter box (as they don't make one in two gang, and two-gang to one-gang mud rings stick out too far) along with one of the BW17 fittings and associated parts to get the raceway going upward from the gang furthest from the inside corner, then use the two flat elbows and the inside elbow to get around the bend and going back down. Then it's just a matter of using the other BW17 and its friends to transition the wires back into the box.



Once the raceway's in, then, you run individual THHN wires inside it to connect the circuits between the two boxes, just as if you were working in conduit. (The existing NM cables can be tossed, or shucked and their wires kept for pigtail duty, your choice.) Don't forget to plug the knockouts where the cables once entered/exited the boxes!



Using some cabinetry to box the boxes



If you feel yourself a better cabinetmaker than electrician, another option for this situation would be to put a cabinet divider wall in just to the right of this, and then add a cabinet door over the front, maintaining access while protecting the existing assembly from physical abuse or damage. This also has the advantage of being a more finished look, at the cost of having an "un-cabinet" in your house that you can't really use for anything at all. Making it match the existing built-in bookshelves may be a challenge, as well.






share|improve this answer














My concern here would be for physical abuse



Right now, nothing stops those NM cables from getting whacked/pinched/crushed with books and such, especially if you have heavy tomes on your shelves. This could be considered a violation of NEC 334.15(A) or (B):




334.15 Exposed Work. In exposed work, except as provided
in 300.11(A), cable shall be installed as specified in 334.15(A)
through (C).



(A) To Follow Surface. Cable shall closely follow the surface
of the building finish or of running boards.



(B) Protection from Physical Damage. Cable shall be protected from physical damage where necessary by rigid metal
conduit, intermediate metal conduit, electrical metallic tubing,
Schedule 80 PVC conduit, Type RTRC marked with the suffix -XW, or other approved means. Where passing through a floor,
the cable shall be enclosed in rigid metal conduit, intermediate
metal conduit, electrical metallic tubing, Schedule 80 PVC
conduit, Type RTRC marked with the suffix -XW, or other
approved means extending at least 150 mm (6 in.) above the
floor.



Type NMC cable installed in shallow chases or grooves in
masonry, concrete, or adobe shall be protected in accordance
with the requirements in 300.4(F) and covered with plaster,
adobe, or similar finish.




You have two options to address this



There are two ways to address this issue: you can either replace the NM cables with a wiring method better suited to withstanding said reader-inflicted physical abuse, or you can put something in that will protect the boxes and cables from rough encounters with books while still allowing for access to them. We'll discuss these options in turn.



Making this more rugged



While the normal wiring methods that are used to withstand the NEC's definition of "physical damage" are the various flavors of heavy-duty rigid conduit (RMC, IMC, EMT, Schedule 80 PVC, and RTRC-XW), surface metal raceway is also rated for such a duty, and doesn't suffer from the bending radius issues that other wiring methods in this application would have to deal with.



If you're using Legrand's Wiremold line for this, you'll need:




  • Two BW17 right angle raceway-to-1/2" conduit fittings, attached with 1/2" chase nipples and locknuts

  • Two BWH6 flat elbows

  • A BWH7 inside elbow

  • A length of BWH1 raceway

  • And a two gang metal extension ring for the old switch box


The idea here is that you use the extension ring instead of the normal starter box (as they don't make one in two gang, and two-gang to one-gang mud rings stick out too far) along with one of the BW17 fittings and associated parts to get the raceway going upward from the gang furthest from the inside corner, then use the two flat elbows and the inside elbow to get around the bend and going back down. Then it's just a matter of using the other BW17 and its friends to transition the wires back into the box.



Once the raceway's in, then, you run individual THHN wires inside it to connect the circuits between the two boxes, just as if you were working in conduit. (The existing NM cables can be tossed, or shucked and their wires kept for pigtail duty, your choice.) Don't forget to plug the knockouts where the cables once entered/exited the boxes!



Using some cabinetry to box the boxes



If you feel yourself a better cabinetmaker than electrician, another option for this situation would be to put a cabinet divider wall in just to the right of this, and then add a cabinet door over the front, maintaining access while protecting the existing assembly from physical abuse or damage. This also has the advantage of being a more finished look, at the cost of having an "un-cabinet" in your house that you can't really use for anything at all. Making it match the existing built-in bookshelves may be a challenge, as well.







share|improve this answer













share|improve this answer




share|improve this answer



share|improve this answer










answered May 27 at 22:58









ThreePhaseEelThreePhaseEel

36.9k11 gold badges56 silver badges111 bronze badges




36.9k11 gold badges56 silver badges111 bronze badges











  • 1





    Wow, thanks for the very detailed answer! Stay tuned for pics of the completed project.

    – TreyGuy
    May 27 at 23:40






  • 5





    @TreyGuy -- we upvote and/or accept folks' answers to show our thanks here :)

    – ThreePhaseEel
    May 27 at 23:41






  • 5





    @TreyGuy -- it's the greyed check below the vote arrows

    – ThreePhaseEel
    May 28 at 1:15






  • 1





    I do love the box it part..And as long as it is easy to get at splice laying there not nailed ..

    – user101687
    May 28 at 6:42






  • 7





    You can find/make fake book spines to cover up the lost space

    – ratchet freak
    May 28 at 11:04














  • 1





    Wow, thanks for the very detailed answer! Stay tuned for pics of the completed project.

    – TreyGuy
    May 27 at 23:40






  • 5





    @TreyGuy -- we upvote and/or accept folks' answers to show our thanks here :)

    – ThreePhaseEel
    May 27 at 23:41






  • 5





    @TreyGuy -- it's the greyed check below the vote arrows

    – ThreePhaseEel
    May 28 at 1:15






  • 1





    I do love the box it part..And as long as it is easy to get at splice laying there not nailed ..

    – user101687
    May 28 at 6:42






  • 7





    You can find/make fake book spines to cover up the lost space

    – ratchet freak
    May 28 at 11:04








1




1





Wow, thanks for the very detailed answer! Stay tuned for pics of the completed project.

– TreyGuy
May 27 at 23:40





Wow, thanks for the very detailed answer! Stay tuned for pics of the completed project.

– TreyGuy
May 27 at 23:40




5




5





@TreyGuy -- we upvote and/or accept folks' answers to show our thanks here :)

– ThreePhaseEel
May 27 at 23:41





@TreyGuy -- we upvote and/or accept folks' answers to show our thanks here :)

– ThreePhaseEel
May 27 at 23:41




5




5





@TreyGuy -- it's the greyed check below the vote arrows

– ThreePhaseEel
May 28 at 1:15





@TreyGuy -- it's the greyed check below the vote arrows

– ThreePhaseEel
May 28 at 1:15




1




1





I do love the box it part..And as long as it is easy to get at splice laying there not nailed ..

– user101687
May 28 at 6:42





I do love the box it part..And as long as it is easy to get at splice laying there not nailed ..

– user101687
May 28 at 6:42




7




7





You can find/make fake book spines to cover up the lost space

– ratchet freak
May 28 at 11:04





You can find/make fake book spines to cover up the lost space

– ratchet freak
May 28 at 11:04













6


















I would go a different way here.



First, the original light switch junction box belongs in the actual wall, not pulled out into the cabinets which themselves could pull out of the wall. I would leave a nice big hole in the cabinet which aligns with the switch box.



They make blank steel cover plates for 2-gang boxes... They are fairly small dimensionally, and they have a 1/2" knockout on their face. I'd come out of that into flexible metal conduit, then the FMC into the back of that 2-gang handy-box you nicely installed.



I'd run 5 individual wires - stranded THHN will handle quite nicely, and one color will suffice since they're all hot (I recommend yellow since it takes colored sharpie well)... plus one green ground. Mark both ends with colored electrical tape or a Sharpie so you can distinguish them.



Wire nut them on to the matching wires inside the wall, send them through the tube, and mount the faceplate on the box that is in the actual wall. Then inside your new box, attach the THHN to switches. The ground goes to the ground screw on the handy-box and that's done. If you use stranded you must not use backstabs! Attaching to screws takes a knack; the best option is a "screw-to-clamp" type switch, where you tighten the screw to attach a back wire.






share|improve this answer



























  • I considered the FMC route, actually -- I felt that the surface metal raceway would offer better protection against damage for this, and I don't think built-in units are going to detach from the wall any time soon if at all adequately fitted...

    – ThreePhaseEel
    May 28 at 0:31






  • 1





    I've lived in earthquake country, built-ins anchored into drywall, that would not surprise me. I actually searched the NEMA plugs for an obscure but available xx-15 /3+gnd socket to make a way for it to plug in... But could not find a plug-socket set that was sanely priced.

    – Harper
    May 28 at 1:08








  • 2





    The cabinets are screwed to the studs, so I really don't think they're going anywhere.

    – TreyGuy
    May 28 at 1:10











  • @Harper -- yeah, the NEMA 14 line starts at 14-20 and goes up from there (and yeah, anchoring built-ins to drywall is a fool's errand in earthquake country IMO)

    – ThreePhaseEel
    May 28 at 1:17











  • Yes I was looking at NEMA 18, 20, odd stuff like 480 wye....That nobody would mistake for residential service...

    – Harper
    May 28 at 12:23
















6


















I would go a different way here.



First, the original light switch junction box belongs in the actual wall, not pulled out into the cabinets which themselves could pull out of the wall. I would leave a nice big hole in the cabinet which aligns with the switch box.



They make blank steel cover plates for 2-gang boxes... They are fairly small dimensionally, and they have a 1/2" knockout on their face. I'd come out of that into flexible metal conduit, then the FMC into the back of that 2-gang handy-box you nicely installed.



I'd run 5 individual wires - stranded THHN will handle quite nicely, and one color will suffice since they're all hot (I recommend yellow since it takes colored sharpie well)... plus one green ground. Mark both ends with colored electrical tape or a Sharpie so you can distinguish them.



Wire nut them on to the matching wires inside the wall, send them through the tube, and mount the faceplate on the box that is in the actual wall. Then inside your new box, attach the THHN to switches. The ground goes to the ground screw on the handy-box and that's done. If you use stranded you must not use backstabs! Attaching to screws takes a knack; the best option is a "screw-to-clamp" type switch, where you tighten the screw to attach a back wire.






share|improve this answer



























  • I considered the FMC route, actually -- I felt that the surface metal raceway would offer better protection against damage for this, and I don't think built-in units are going to detach from the wall any time soon if at all adequately fitted...

    – ThreePhaseEel
    May 28 at 0:31






  • 1





    I've lived in earthquake country, built-ins anchored into drywall, that would not surprise me. I actually searched the NEMA plugs for an obscure but available xx-15 /3+gnd socket to make a way for it to plug in... But could not find a plug-socket set that was sanely priced.

    – Harper
    May 28 at 1:08








  • 2





    The cabinets are screwed to the studs, so I really don't think they're going anywhere.

    – TreyGuy
    May 28 at 1:10











  • @Harper -- yeah, the NEMA 14 line starts at 14-20 and goes up from there (and yeah, anchoring built-ins to drywall is a fool's errand in earthquake country IMO)

    – ThreePhaseEel
    May 28 at 1:17











  • Yes I was looking at NEMA 18, 20, odd stuff like 480 wye....That nobody would mistake for residential service...

    – Harper
    May 28 at 12:23














6














6










6









I would go a different way here.



First, the original light switch junction box belongs in the actual wall, not pulled out into the cabinets which themselves could pull out of the wall. I would leave a nice big hole in the cabinet which aligns with the switch box.



They make blank steel cover plates for 2-gang boxes... They are fairly small dimensionally, and they have a 1/2" knockout on their face. I'd come out of that into flexible metal conduit, then the FMC into the back of that 2-gang handy-box you nicely installed.



I'd run 5 individual wires - stranded THHN will handle quite nicely, and one color will suffice since they're all hot (I recommend yellow since it takes colored sharpie well)... plus one green ground. Mark both ends with colored electrical tape or a Sharpie so you can distinguish them.



Wire nut them on to the matching wires inside the wall, send them through the tube, and mount the faceplate on the box that is in the actual wall. Then inside your new box, attach the THHN to switches. The ground goes to the ground screw on the handy-box and that's done. If you use stranded you must not use backstabs! Attaching to screws takes a knack; the best option is a "screw-to-clamp" type switch, where you tighten the screw to attach a back wire.






share|improve this answer














I would go a different way here.



First, the original light switch junction box belongs in the actual wall, not pulled out into the cabinets which themselves could pull out of the wall. I would leave a nice big hole in the cabinet which aligns with the switch box.



They make blank steel cover plates for 2-gang boxes... They are fairly small dimensionally, and they have a 1/2" knockout on their face. I'd come out of that into flexible metal conduit, then the FMC into the back of that 2-gang handy-box you nicely installed.



I'd run 5 individual wires - stranded THHN will handle quite nicely, and one color will suffice since they're all hot (I recommend yellow since it takes colored sharpie well)... plus one green ground. Mark both ends with colored electrical tape or a Sharpie so you can distinguish them.



Wire nut them on to the matching wires inside the wall, send them through the tube, and mount the faceplate on the box that is in the actual wall. Then inside your new box, attach the THHN to switches. The ground goes to the ground screw on the handy-box and that's done. If you use stranded you must not use backstabs! Attaching to screws takes a knack; the best option is a "screw-to-clamp" type switch, where you tighten the screw to attach a back wire.







share|improve this answer













share|improve this answer




share|improve this answer



share|improve this answer










answered May 28 at 0:10









HarperHarper

99.8k7 gold badges75 silver badges211 bronze badges




99.8k7 gold badges75 silver badges211 bronze badges
















  • I considered the FMC route, actually -- I felt that the surface metal raceway would offer better protection against damage for this, and I don't think built-in units are going to detach from the wall any time soon if at all adequately fitted...

    – ThreePhaseEel
    May 28 at 0:31






  • 1





    I've lived in earthquake country, built-ins anchored into drywall, that would not surprise me. I actually searched the NEMA plugs for an obscure but available xx-15 /3+gnd socket to make a way for it to plug in... But could not find a plug-socket set that was sanely priced.

    – Harper
    May 28 at 1:08








  • 2





    The cabinets are screwed to the studs, so I really don't think they're going anywhere.

    – TreyGuy
    May 28 at 1:10











  • @Harper -- yeah, the NEMA 14 line starts at 14-20 and goes up from there (and yeah, anchoring built-ins to drywall is a fool's errand in earthquake country IMO)

    – ThreePhaseEel
    May 28 at 1:17











  • Yes I was looking at NEMA 18, 20, odd stuff like 480 wye....That nobody would mistake for residential service...

    – Harper
    May 28 at 12:23



















  • I considered the FMC route, actually -- I felt that the surface metal raceway would offer better protection against damage for this, and I don't think built-in units are going to detach from the wall any time soon if at all adequately fitted...

    – ThreePhaseEel
    May 28 at 0:31






  • 1





    I've lived in earthquake country, built-ins anchored into drywall, that would not surprise me. I actually searched the NEMA plugs for an obscure but available xx-15 /3+gnd socket to make a way for it to plug in... But could not find a plug-socket set that was sanely priced.

    – Harper
    May 28 at 1:08








  • 2





    The cabinets are screwed to the studs, so I really don't think they're going anywhere.

    – TreyGuy
    May 28 at 1:10











  • @Harper -- yeah, the NEMA 14 line starts at 14-20 and goes up from there (and yeah, anchoring built-ins to drywall is a fool's errand in earthquake country IMO)

    – ThreePhaseEel
    May 28 at 1:17











  • Yes I was looking at NEMA 18, 20, odd stuff like 480 wye....That nobody would mistake for residential service...

    – Harper
    May 28 at 12:23

















I considered the FMC route, actually -- I felt that the surface metal raceway would offer better protection against damage for this, and I don't think built-in units are going to detach from the wall any time soon if at all adequately fitted...

– ThreePhaseEel
May 28 at 0:31





I considered the FMC route, actually -- I felt that the surface metal raceway would offer better protection against damage for this, and I don't think built-in units are going to detach from the wall any time soon if at all adequately fitted...

– ThreePhaseEel
May 28 at 0:31




1




1





I've lived in earthquake country, built-ins anchored into drywall, that would not surprise me. I actually searched the NEMA plugs for an obscure but available xx-15 /3+gnd socket to make a way for it to plug in... But could not find a plug-socket set that was sanely priced.

– Harper
May 28 at 1:08







I've lived in earthquake country, built-ins anchored into drywall, that would not surprise me. I actually searched the NEMA plugs for an obscure but available xx-15 /3+gnd socket to make a way for it to plug in... But could not find a plug-socket set that was sanely priced.

– Harper
May 28 at 1:08






2




2





The cabinets are screwed to the studs, so I really don't think they're going anywhere.

– TreyGuy
May 28 at 1:10





The cabinets are screwed to the studs, so I really don't think they're going anywhere.

– TreyGuy
May 28 at 1:10













@Harper -- yeah, the NEMA 14 line starts at 14-20 and goes up from there (and yeah, anchoring built-ins to drywall is a fool's errand in earthquake country IMO)

– ThreePhaseEel
May 28 at 1:17





@Harper -- yeah, the NEMA 14 line starts at 14-20 and goes up from there (and yeah, anchoring built-ins to drywall is a fool's errand in earthquake country IMO)

– ThreePhaseEel
May 28 at 1:17













Yes I was looking at NEMA 18, 20, odd stuff like 480 wye....That nobody would mistake for residential service...

– Harper
May 28 at 12:23





Yes I was looking at NEMA 18, 20, odd stuff like 480 wye....That nobody would mistake for residential service...

– Harper
May 28 at 12:23











3


















Another option would eminate the wiring altogether! Goconex (now Nevven) makes a wireless system that would give you all you space back. Two small controllers, actually small receiver/relay units, are wired into the circuits in the ganged box, the romex to the handy box pulled and discarded. The handy box can stay or not, as you wish, but if pulled a plain plate can cover the hole. Finally, two transmitter switches can be mounted in the same place as were the old switches. These appear to be standard Decora rocker switches, same mounting format, but have ZERO rear protrusion, can mount on a box or completely surface mounted. The entire switch unit fits behind a standard switchplate and is still flush with the wall. You can mount the switches anywhere within 100' (maybe you really never wanted them there?) Or add another switch? One switch can discriminately operate an infinite number of relays or one relay can be controlled by up to five switches.Batteries in the remote switches are said to last 10-15 yrs.






share|improve this answer



























  • I have this type of switch (although a different brand), and batteries only last around a year of bathroom type of use. They also use more expensive 12V batteries.

    – George Y.
    May 28 at 19:15











  • MK make a wireless battery-less switch which is piezo-powered. But it needs specialist receiver equipment and is quite expensive. This answer may be describing something similar for the US market.

    – Andrew Leach
    May 28 at 19:30











  • Great suggestion. Electricians don't usually think of, let alone consider, wireless solutions. (Errr, does "eminate" mean "eliminate"?)

    – wallyk
    May 29 at 16:46


















3


















Another option would eminate the wiring altogether! Goconex (now Nevven) makes a wireless system that would give you all you space back. Two small controllers, actually small receiver/relay units, are wired into the circuits in the ganged box, the romex to the handy box pulled and discarded. The handy box can stay or not, as you wish, but if pulled a plain plate can cover the hole. Finally, two transmitter switches can be mounted in the same place as were the old switches. These appear to be standard Decora rocker switches, same mounting format, but have ZERO rear protrusion, can mount on a box or completely surface mounted. The entire switch unit fits behind a standard switchplate and is still flush with the wall. You can mount the switches anywhere within 100' (maybe you really never wanted them there?) Or add another switch? One switch can discriminately operate an infinite number of relays or one relay can be controlled by up to five switches.Batteries in the remote switches are said to last 10-15 yrs.






share|improve this answer



























  • I have this type of switch (although a different brand), and batteries only last around a year of bathroom type of use. They also use more expensive 12V batteries.

    – George Y.
    May 28 at 19:15











  • MK make a wireless battery-less switch which is piezo-powered. But it needs specialist receiver equipment and is quite expensive. This answer may be describing something similar for the US market.

    – Andrew Leach
    May 28 at 19:30











  • Great suggestion. Electricians don't usually think of, let alone consider, wireless solutions. (Errr, does "eminate" mean "eliminate"?)

    – wallyk
    May 29 at 16:46
















3














3










3









Another option would eminate the wiring altogether! Goconex (now Nevven) makes a wireless system that would give you all you space back. Two small controllers, actually small receiver/relay units, are wired into the circuits in the ganged box, the romex to the handy box pulled and discarded. The handy box can stay or not, as you wish, but if pulled a plain plate can cover the hole. Finally, two transmitter switches can be mounted in the same place as were the old switches. These appear to be standard Decora rocker switches, same mounting format, but have ZERO rear protrusion, can mount on a box or completely surface mounted. The entire switch unit fits behind a standard switchplate and is still flush with the wall. You can mount the switches anywhere within 100' (maybe you really never wanted them there?) Or add another switch? One switch can discriminately operate an infinite number of relays or one relay can be controlled by up to five switches.Batteries in the remote switches are said to last 10-15 yrs.






share|improve this answer














Another option would eminate the wiring altogether! Goconex (now Nevven) makes a wireless system that would give you all you space back. Two small controllers, actually small receiver/relay units, are wired into the circuits in the ganged box, the romex to the handy box pulled and discarded. The handy box can stay or not, as you wish, but if pulled a plain plate can cover the hole. Finally, two transmitter switches can be mounted in the same place as were the old switches. These appear to be standard Decora rocker switches, same mounting format, but have ZERO rear protrusion, can mount on a box or completely surface mounted. The entire switch unit fits behind a standard switchplate and is still flush with the wall. You can mount the switches anywhere within 100' (maybe you really never wanted them there?) Or add another switch? One switch can discriminately operate an infinite number of relays or one relay can be controlled by up to five switches.Batteries in the remote switches are said to last 10-15 yrs.







share|improve this answer













share|improve this answer




share|improve this answer



share|improve this answer










answered May 28 at 16:16









Gregory L BlackmanGregory L Blackman

311 bronze badge




311 bronze badge
















  • I have this type of switch (although a different brand), and batteries only last around a year of bathroom type of use. They also use more expensive 12V batteries.

    – George Y.
    May 28 at 19:15











  • MK make a wireless battery-less switch which is piezo-powered. But it needs specialist receiver equipment and is quite expensive. This answer may be describing something similar for the US market.

    – Andrew Leach
    May 28 at 19:30











  • Great suggestion. Electricians don't usually think of, let alone consider, wireless solutions. (Errr, does "eminate" mean "eliminate"?)

    – wallyk
    May 29 at 16:46





















  • I have this type of switch (although a different brand), and batteries only last around a year of bathroom type of use. They also use more expensive 12V batteries.

    – George Y.
    May 28 at 19:15











  • MK make a wireless battery-less switch which is piezo-powered. But it needs specialist receiver equipment and is quite expensive. This answer may be describing something similar for the US market.

    – Andrew Leach
    May 28 at 19:30











  • Great suggestion. Electricians don't usually think of, let alone consider, wireless solutions. (Errr, does "eminate" mean "eliminate"?)

    – wallyk
    May 29 at 16:46



















I have this type of switch (although a different brand), and batteries only last around a year of bathroom type of use. They also use more expensive 12V batteries.

– George Y.
May 28 at 19:15





I have this type of switch (although a different brand), and batteries only last around a year of bathroom type of use. They also use more expensive 12V batteries.

– George Y.
May 28 at 19:15













MK make a wireless battery-less switch which is piezo-powered. But it needs specialist receiver equipment and is quite expensive. This answer may be describing something similar for the US market.

– Andrew Leach
May 28 at 19:30





MK make a wireless battery-less switch which is piezo-powered. But it needs specialist receiver equipment and is quite expensive. This answer may be describing something similar for the US market.

– Andrew Leach
May 28 at 19:30













Great suggestion. Electricians don't usually think of, let alone consider, wireless solutions. (Errr, does "eminate" mean "eliminate"?)

– wallyk
May 29 at 16:46







Great suggestion. Electricians don't usually think of, let alone consider, wireless solutions. (Errr, does "eminate" mean "eliminate"?)

– wallyk
May 29 at 16:46













1


















I'm not sure why almost everyone is wanting to make your solution be expensive. Do a Google search for 2 gang electrical extension ring. Very simple to install. Keeps everything contained in your original wall box, but provides you the ability to extend the box into the bookcase.



Side note bookcase must be secured to the structure to be legal. Even though you didn't have to use the UF cable it can still be used in this application. You just turn OFF POWER, pull switches out, label wires with masking tape,( S1U, S1L,S2U, S-- switch, 1 or 2- left or right switch your choice, U,L- upper or lower power connection screws on the switches. Remove wires from the switches. Then remove the box that you used in the bookcase, get all wiring to come back into the original wall box. Use push plugs to close any holes in the wall box that are not being utilized for the incoming original wiring. Push all wiring back into original wall box to ensure safety of existing wire from damage, make sure hole in bookcase is aligned with original wall box, Install extension ring into hole in bookcase, push bookcase into place, attach extension ring to original wall box and then resecure bookcase to the structure, pull all wire back out through the extension ring, re-install wiring to the switches, add electrical tape around exterior of each switch, covering the power connection screws,. (Safety). Attach switches to extension ring, and reinstall wall plate. Ensure both switches are in the off position, turn power back on from source. Turn each switch on individually.



Everything should work as intended, but by turning each one on individually, if there is an issue, it will be easier to deduce if a problem exists. The most important thing to remember is to never work on a live circuit unless it is absolutely necessary. Any good electrical tradesman will express the same sentiments. We know how to work on live circuitry but try our best not to if possible. No reason to be another accident statistic when it's preventable. Leviton 42777-2WB is one example of an extension ring that could be used in this application






share|improve this answer
























  • 2





    Hello, and welcome to Home Improvement. This is interesting, but is hard to read as a long Wall 'O' Text. You might want to edit it to make it clearer; please take our tour so you'll know how better to contribute here.

    – Daniel Griscom
    May 29 at 14:19
















1


















I'm not sure why almost everyone is wanting to make your solution be expensive. Do a Google search for 2 gang electrical extension ring. Very simple to install. Keeps everything contained in your original wall box, but provides you the ability to extend the box into the bookcase.



Side note bookcase must be secured to the structure to be legal. Even though you didn't have to use the UF cable it can still be used in this application. You just turn OFF POWER, pull switches out, label wires with masking tape,( S1U, S1L,S2U, S-- switch, 1 or 2- left or right switch your choice, U,L- upper or lower power connection screws on the switches. Remove wires from the switches. Then remove the box that you used in the bookcase, get all wiring to come back into the original wall box. Use push plugs to close any holes in the wall box that are not being utilized for the incoming original wiring. Push all wiring back into original wall box to ensure safety of existing wire from damage, make sure hole in bookcase is aligned with original wall box, Install extension ring into hole in bookcase, push bookcase into place, attach extension ring to original wall box and then resecure bookcase to the structure, pull all wire back out through the extension ring, re-install wiring to the switches, add electrical tape around exterior of each switch, covering the power connection screws,. (Safety). Attach switches to extension ring, and reinstall wall plate. Ensure both switches are in the off position, turn power back on from source. Turn each switch on individually.



Everything should work as intended, but by turning each one on individually, if there is an issue, it will be easier to deduce if a problem exists. The most important thing to remember is to never work on a live circuit unless it is absolutely necessary. Any good electrical tradesman will express the same sentiments. We know how to work on live circuitry but try our best not to if possible. No reason to be another accident statistic when it's preventable. Leviton 42777-2WB is one example of an extension ring that could be used in this application






share|improve this answer
























  • 2





    Hello, and welcome to Home Improvement. This is interesting, but is hard to read as a long Wall 'O' Text. You might want to edit it to make it clearer; please take our tour so you'll know how better to contribute here.

    – Daniel Griscom
    May 29 at 14:19














1














1










1









I'm not sure why almost everyone is wanting to make your solution be expensive. Do a Google search for 2 gang electrical extension ring. Very simple to install. Keeps everything contained in your original wall box, but provides you the ability to extend the box into the bookcase.



Side note bookcase must be secured to the structure to be legal. Even though you didn't have to use the UF cable it can still be used in this application. You just turn OFF POWER, pull switches out, label wires with masking tape,( S1U, S1L,S2U, S-- switch, 1 or 2- left or right switch your choice, U,L- upper or lower power connection screws on the switches. Remove wires from the switches. Then remove the box that you used in the bookcase, get all wiring to come back into the original wall box. Use push plugs to close any holes in the wall box that are not being utilized for the incoming original wiring. Push all wiring back into original wall box to ensure safety of existing wire from damage, make sure hole in bookcase is aligned with original wall box, Install extension ring into hole in bookcase, push bookcase into place, attach extension ring to original wall box and then resecure bookcase to the structure, pull all wire back out through the extension ring, re-install wiring to the switches, add electrical tape around exterior of each switch, covering the power connection screws,. (Safety). Attach switches to extension ring, and reinstall wall plate. Ensure both switches are in the off position, turn power back on from source. Turn each switch on individually.



Everything should work as intended, but by turning each one on individually, if there is an issue, it will be easier to deduce if a problem exists. The most important thing to remember is to never work on a live circuit unless it is absolutely necessary. Any good electrical tradesman will express the same sentiments. We know how to work on live circuitry but try our best not to if possible. No reason to be another accident statistic when it's preventable. Leviton 42777-2WB is one example of an extension ring that could be used in this application






share|improve this answer
















I'm not sure why almost everyone is wanting to make your solution be expensive. Do a Google search for 2 gang electrical extension ring. Very simple to install. Keeps everything contained in your original wall box, but provides you the ability to extend the box into the bookcase.



Side note bookcase must be secured to the structure to be legal. Even though you didn't have to use the UF cable it can still be used in this application. You just turn OFF POWER, pull switches out, label wires with masking tape,( S1U, S1L,S2U, S-- switch, 1 or 2- left or right switch your choice, U,L- upper or lower power connection screws on the switches. Remove wires from the switches. Then remove the box that you used in the bookcase, get all wiring to come back into the original wall box. Use push plugs to close any holes in the wall box that are not being utilized for the incoming original wiring. Push all wiring back into original wall box to ensure safety of existing wire from damage, make sure hole in bookcase is aligned with original wall box, Install extension ring into hole in bookcase, push bookcase into place, attach extension ring to original wall box and then resecure bookcase to the structure, pull all wire back out through the extension ring, re-install wiring to the switches, add electrical tape around exterior of each switch, covering the power connection screws,. (Safety). Attach switches to extension ring, and reinstall wall plate. Ensure both switches are in the off position, turn power back on from source. Turn each switch on individually.



Everything should work as intended, but by turning each one on individually, if there is an issue, it will be easier to deduce if a problem exists. The most important thing to remember is to never work on a live circuit unless it is absolutely necessary. Any good electrical tradesman will express the same sentiments. We know how to work on live circuitry but try our best not to if possible. No reason to be another accident statistic when it's preventable. Leviton 42777-2WB is one example of an extension ring that could be used in this application







share|improve this answer















share|improve this answer




share|improve this answer



share|improve this answer








edited May 29 at 22:29









donjuedo

2422 silver badges7 bronze badges




2422 silver badges7 bronze badges










answered May 29 at 11:40









Michael SkaerMichael Skaer

111 bronze badge




111 bronze badge











  • 2





    Hello, and welcome to Home Improvement. This is interesting, but is hard to read as a long Wall 'O' Text. You might want to edit it to make it clearer; please take our tour so you'll know how better to contribute here.

    – Daniel Griscom
    May 29 at 14:19














  • 2





    Hello, and welcome to Home Improvement. This is interesting, but is hard to read as a long Wall 'O' Text. You might want to edit it to make it clearer; please take our tour so you'll know how better to contribute here.

    – Daniel Griscom
    May 29 at 14:19








2




2





Hello, and welcome to Home Improvement. This is interesting, but is hard to read as a long Wall 'O' Text. You might want to edit it to make it clearer; please take our tour so you'll know how better to contribute here.

– Daniel Griscom
May 29 at 14:19





Hello, and welcome to Home Improvement. This is interesting, but is hard to read as a long Wall 'O' Text. You might want to edit it to make it clearer; please take our tour so you'll know how better to contribute here.

– Daniel Griscom
May 29 at 14:19











0


















Any exposed wire need to be covered or inclosed, wood box and slid it over the wires. I am more concerned with grounding in the metal box without a ground screw in the box you run the risk of electrocution.






share|improve this answer



























  • The box in back, at least, is likely grounded through the metal ground clip visible on the right side of the box.

    – ThreePhaseEel
    May 28 at 22:39
















0


















Any exposed wire need to be covered or inclosed, wood box and slid it over the wires. I am more concerned with grounding in the metal box without a ground screw in the box you run the risk of electrocution.






share|improve this answer



























  • The box in back, at least, is likely grounded through the metal ground clip visible on the right side of the box.

    – ThreePhaseEel
    May 28 at 22:39














0














0










0









Any exposed wire need to be covered or inclosed, wood box and slid it over the wires. I am more concerned with grounding in the metal box without a ground screw in the box you run the risk of electrocution.






share|improve this answer














Any exposed wire need to be covered or inclosed, wood box and slid it over the wires. I am more concerned with grounding in the metal box without a ground screw in the box you run the risk of electrocution.







share|improve this answer













share|improve this answer




share|improve this answer



share|improve this answer










answered May 28 at 12:18









Stephen AlfordStephen Alford

1




1
















  • The box in back, at least, is likely grounded through the metal ground clip visible on the right side of the box.

    – ThreePhaseEel
    May 28 at 22:39



















  • The box in back, at least, is likely grounded through the metal ground clip visible on the right side of the box.

    – ThreePhaseEel
    May 28 at 22:39

















The box in back, at least, is likely grounded through the metal ground clip visible on the right side of the box.

– ThreePhaseEel
May 28 at 22:39





The box in back, at least, is likely grounded through the metal ground clip visible on the right side of the box.

– ThreePhaseEel
May 28 at 22:39











0


















Use wire mold and come out of the top, go to the right, around the corner and back down. Drill a hole in the center of the faceplate (maybe get a metal faceplate if you need it) and use a 90° wiremold connector or use a 4" surface mount box (the kind that is made to use with wire mold) and come in to the top. Or do the same thing but with MC cable. You may need 12/3 or 12/4 depending on how many conductors you need. If it's just 1 switch you can use 12/2 and use the white as your switch leg but new code says you're not supposed to do that. You could always box in that corner but technically the "junction box" needs to be accessible. But if you're not getting an inspection then it's up to you. Ground those metal boxes!






share|improve this answer





























  • It looks like the box in back is grounded via the grounding clip visible on the right side of the box...

    – ThreePhaseEel
    May 28 at 22:18
















0


















Use wire mold and come out of the top, go to the right, around the corner and back down. Drill a hole in the center of the faceplate (maybe get a metal faceplate if you need it) and use a 90° wiremold connector or use a 4" surface mount box (the kind that is made to use with wire mold) and come in to the top. Or do the same thing but with MC cable. You may need 12/3 or 12/4 depending on how many conductors you need. If it's just 1 switch you can use 12/2 and use the white as your switch leg but new code says you're not supposed to do that. You could always box in that corner but technically the "junction box" needs to be accessible. But if you're not getting an inspection then it's up to you. Ground those metal boxes!






share|improve this answer





























  • It looks like the box in back is grounded via the grounding clip visible on the right side of the box...

    – ThreePhaseEel
    May 28 at 22:18














0














0










0









Use wire mold and come out of the top, go to the right, around the corner and back down. Drill a hole in the center of the faceplate (maybe get a metal faceplate if you need it) and use a 90° wiremold connector or use a 4" surface mount box (the kind that is made to use with wire mold) and come in to the top. Or do the same thing but with MC cable. You may need 12/3 or 12/4 depending on how many conductors you need. If it's just 1 switch you can use 12/2 and use the white as your switch leg but new code says you're not supposed to do that. You could always box in that corner but technically the "junction box" needs to be accessible. But if you're not getting an inspection then it's up to you. Ground those metal boxes!






share|improve this answer
















Use wire mold and come out of the top, go to the right, around the corner and back down. Drill a hole in the center of the faceplate (maybe get a metal faceplate if you need it) and use a 90° wiremold connector or use a 4" surface mount box (the kind that is made to use with wire mold) and come in to the top. Or do the same thing but with MC cable. You may need 12/3 or 12/4 depending on how many conductors you need. If it's just 1 switch you can use 12/2 and use the white as your switch leg but new code says you're not supposed to do that. You could always box in that corner but technically the "junction box" needs to be accessible. But if you're not getting an inspection then it's up to you. Ground those metal boxes!







share|improve this answer















share|improve this answer




share|improve this answer



share|improve this answer








edited May 28 at 20:57

























answered May 28 at 20:20









Jeffrey Keith JohnstonJeffrey Keith Johnston

11 bronze badge




11 bronze badge
















  • It looks like the box in back is grounded via the grounding clip visible on the right side of the box...

    – ThreePhaseEel
    May 28 at 22:18



















  • It looks like the box in back is grounded via the grounding clip visible on the right side of the box...

    – ThreePhaseEel
    May 28 at 22:18

















It looks like the box in back is grounded via the grounding clip visible on the right side of the box...

– ThreePhaseEel
May 28 at 22:18





It looks like the box in back is grounded via the grounding clip visible on the right side of the box...

– ThreePhaseEel
May 28 at 22:18



















draft saved

draft discarded



















































Thanks for contributing an answer to Home Improvement Stack Exchange!


  • Please be sure to answer the question. Provide details and share your research!

But avoid



  • Asking for help, clarification, or responding to other answers.

  • Making statements based on opinion; back them up with references or personal experience.


To learn more, see our tips on writing great answers.




draft saved


draft discarded














StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f166001%2fis-this-light-switch-installation-safe-and-legal%23new-answer', 'question_page');
}
);

Post as a guest















Required, but never shown





















































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown

































Required, but never shown














Required, but never shown












Required, but never shown







Required, but never shown









Popular posts from this blog

Færeyskur hestur Heimild | Tengill | Tilvísanir | LeiðsagnarvalRossið - síða um færeyska hrossið á færeyskuGott ár hjá færeyska hestinum

He _____ here since 1970 . Answer needed [closed]What does “since he was so high” mean?Meaning of “catch birds for”?How do I ensure “since” takes the meaning I want?“Who cares here” meaningWhat does “right round toward” mean?the time tense (had now been detected)What does the phrase “ring around the roses” mean here?Correct usage of “visited upon”Meaning of “foiled rail sabotage bid”It was the third time I had gone to Rome or It is the third time I had been to Rome

Slayer Innehåll Historia | Stil, komposition och lyrik | Bandets betydelse och framgångar | Sidoprojekt och samarbeten | Kontroverser | Medlemmar | Utmärkelser och nomineringar | Turnéer och festivaler | Diskografi | Referenser | Externa länkar | Navigeringsmenywww.slayer.net”Metal Massacre vol. 1””Metal Massacre vol. 3””Metal Massacre Volume III””Show No Mercy””Haunting the Chapel””Live Undead””Hell Awaits””Reign in Blood””Reign in Blood””Gold & Platinum – Reign in Blood””Golden Gods Awards Winners”originalet”Kerrang! Hall Of Fame””Slayer Looks Back On 37-Year Career In New Video Series: Part Two””South of Heaven””Gold & Platinum – South of Heaven””Seasons in the Abyss””Gold & Platinum - Seasons in the Abyss””Divine Intervention””Divine Intervention - Release group by Slayer””Gold & Platinum - Divine Intervention””Live Intrusion””Undisputed Attitude””Abolish Government/Superficial Love””Release “Slatanic Slaughter: A Tribute to Slayer” by Various Artists””Diabolus in Musica””Soundtrack to the Apocalypse””God Hates Us All””Systematic - Relationships””War at the Warfield””Gold & Platinum - War at the Warfield””Soundtrack to the Apocalypse””Gold & Platinum - Still Reigning””Metallica, Slayer, Iron Mauden Among Winners At Metal Hammer Awards””Eternal Pyre””Eternal Pyre - Slayer release group””Eternal Pyre””Metal Storm Awards 2006””Kerrang! Hall Of Fame””Slayer Wins 'Best Metal' Grammy Award””Slayer Guitarist Jeff Hanneman Dies””Bullet-For My Valentine booed at Metal Hammer Golden Gods Awards””Unholy Aliance””The End Of Slayer?””Slayer: We Could Thrash Out Two More Albums If We're Fast Enough...””'The Unholy Alliance: Chapter III' UK Dates Added”originalet”Megadeth And Slayer To Co-Headline 'Canadian Carnage' Trek”originalet”World Painted Blood””Release “World Painted Blood” by Slayer””Metallica Heading To Cinemas””Slayer, Megadeth To Join Forces For 'European Carnage' Tour - Dec. 18, 2010”originalet”Slayer's Hanneman Contracts Acute Infection; Band To Bring In Guest Guitarist””Cannibal Corpse's Pat O'Brien Will Step In As Slayer's Guest Guitarist”originalet”Slayer’s Jeff Hanneman Dead at 49””Dave Lombardo Says He Made Only $67,000 In 2011 While Touring With Slayer””Slayer: We Do Not Agree With Dave Lombardo's Substance Or Timeline Of Events””Slayer Welcomes Drummer Paul Bostaph Back To The Fold””Slayer Hope to Unveil Never-Before-Heard Jeff Hanneman Material on Next Album””Slayer Debut New Song 'Implode' During Surprise Golden Gods Appearance””Release group Repentless by Slayer””Repentless - Slayer - Credits””Slayer””Metal Storm Awards 2015””Slayer - to release comic book "Repentless #1"””Slayer To Release 'Repentless' 6.66" Vinyl Box Set””BREAKING NEWS: Slayer Announce Farewell Tour””Slayer Recruit Lamb of God, Anthrax, Behemoth + Testament for Final Tour””Slayer lägger ner efter 37 år””Slayer Announces Second North American Leg Of 'Final' Tour””Final World Tour””Slayer Announces Final European Tour With Lamb of God, Anthrax And Obituary””Slayer To Tour Europe With Lamb of God, Anthrax And Obituary””Slayer To Play 'Last French Show Ever' At Next Year's Hellfst””Slayer's Final World Tour Will Extend Into 2019””Death Angel's Rob Cavestany On Slayer's 'Farewell' Tour: 'Some Of Us Could See This Coming'””Testament Has No Plans To Retire Anytime Soon, Says Chuck Billy””Anthrax's Scott Ian On Slayer's 'Farewell' Tour Plans: 'I Was Surprised And I Wasn't Surprised'””Slayer””Slayer's Morbid Schlock””Review/Rock; For Slayer, the Mania Is the Message””Slayer - Biography””Slayer - Reign In Blood”originalet”Dave Lombardo””An exclusive oral history of Slayer”originalet”Exclusive! Interview With Slayer Guitarist Jeff Hanneman”originalet”Thinking Out Loud: Slayer's Kerry King on hair metal, Satan and being polite””Slayer Lyrics””Slayer - Biography””Most influential artists for extreme metal music””Slayer - Reign in Blood””Slayer guitarist Jeff Hanneman dies aged 49””Slatanic Slaughter: A Tribute to Slayer””Gateway to Hell: A Tribute to Slayer””Covered In Blood””Slayer: The Origins of Thrash in San Francisco, CA.””Why They Rule - #6 Slayer”originalet”Guitar World's 100 Greatest Heavy Metal Guitarists Of All Time”originalet”The fans have spoken: Slayer comes out on top in readers' polls”originalet”Tribute to Jeff Hanneman (1964-2013)””Lamb Of God Frontman: We Sound Like A Slayer Rip-Off””BEHEMOTH Frontman Pays Tribute To SLAYER's JEFF HANNEMAN””Slayer, Hatebreed Doing Double Duty On This Year's Ozzfest””System of a Down””Lacuna Coil’s Andrea Ferro Talks Influences, Skateboarding, Band Origins + More””Slayer - Reign in Blood””Into The Lungs of Hell””Slayer rules - en utställning om fans””Slayer and Their Fans Slashed Through a No-Holds-Barred Night at Gas Monkey””Home””Slayer””Gold & Platinum - The Big 4 Live from Sofia, Bulgaria””Exclusive! Interview With Slayer Guitarist Kerry King””2008-02-23: Wiltern, Los Angeles, CA, USA””Slayer's Kerry King To Perform With Megadeth Tonight! - Oct. 21, 2010”originalet”Dave Lombardo - Biography”Slayer Case DismissedArkiveradUltimate Classic Rock: Slayer guitarist Jeff Hanneman dead at 49.”Slayer: "We could never do any thing like Some Kind Of Monster..."””Cannibal Corpse'S Pat O'Brien Will Step In As Slayer'S Guest Guitarist | The Official Slayer Site”originalet”Slayer Wins 'Best Metal' Grammy Award””Slayer Guitarist Jeff Hanneman Dies””Kerrang! Awards 2006 Blog: Kerrang! Hall Of Fame””Kerrang! Awards 2013: Kerrang! Legend”originalet”Metallica, Slayer, Iron Maien Among Winners At Metal Hammer Awards””Metal Hammer Golden Gods Awards””Bullet For My Valentine Booed At Metal Hammer Golden Gods Awards””Metal Storm Awards 2006””Metal Storm Awards 2015””Slayer's Concert History””Slayer - Relationships””Slayer - Releases”Slayers officiella webbplatsSlayer på MusicBrainzOfficiell webbplatsSlayerSlayerr1373445760000 0001 1540 47353068615-5086262726cb13906545x(data)6033143kn20030215029